Inspections for the day of: Thursday, November 1, 2001.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00531 INSP-Sprinkler Rough-in/Hydro10/31/200111/1/200111/1/2001 12:00:00 AMAPASS
Sprinkler rough-in OK, annual inspection to be provided for the existing riser 11/1/2001 9:29:37 AM
FIR01-00530 INSP-Sprinkler Rough-in/Hydro10/31/200111/1/200111/1/2001 12:00:00 AMAPASS
Sprinkler rough-in OK . Annual inspection to be provided for existing riser 11/1/2001 9:15:44 AM 11/1/2001 9:28:54 AM
BLD01-02555 BLD-Final11/1/200111/1/200111/1/2001 12:00:00 AMAPASS
Added by Inspector: 430 On 11/1/2001 11:57:50 AM Fire/Life Safety OK for perm occ
FIR01-00360 INSP-Sprinkler Rough-in/Hydro11/1/200111/1/200111/1/2001 12:00:00 AMPPASS
Added by Inspector: 430 On 11/1/2001 2:49:14 PM above ground hydro test ok
BLD01-00144 FIRE-Alarm Testing10/31/200111/1/200111/1/2001 12:00:00 AMPCANC
Duplicate inspection 11/2/2001 11:53:46 AM
BLD01-00144 FIRE-Final Inspection10/31/200111/1/200111/1/2001 12:00:00 AMPFAIL
Fire/smoke damper needs to be wired, no approved plans on site, backflow preventor on sprinkler system not operating correctly 11/2/2001 11:54:49 AM
BLD01-02187 FIRE-Final Inspection11/1/200111/1/200111/1/2001 12:00:00 AMPFAIL
North exit needs thumb turn removed and door knob replace, dead bolt in restroom to be removed, HVAC unit verification (2000 cfm), provide knox box, suite number, fire alarm horn strobe to be in occupied area. Did not get access to fire sprinkler room 11/1/2001 5:07:16 PM
BLD00-00663 FIRE-Final Inspection11/1/200111/1/200111/1/2001 12:00:00 AMPFAIL
tim- ###-####-- Contractor to remove hardware from inner doors of weather vestible and install Fire Lane sign at entrance 11/1/2001 11:41:27 AM
MIS01-00215 FIR-Final11/1/200111/1/200111/1/2001 12:00:00 AMPFAIL
Cindy, ###-#### Emergency lights to be provided in three rooms, fire exting. to be lowered, exit lights to be at both exterior doors, HVAC system (2000cfm) needs to be verified, central door needs to be removed or door hardware changed. Structural inspector to review ADA requirements. 11/1/2001 5:09:55 PM