BLD04-00558
| FIRE-Final Inspection | 10/29/2004 | 11/1/2004 | 11/1/2004 12:00:00 AM | A | FAIL |
|
|
Need to final fire alarm and fire sprinklers. Verify life safety compiance in all tenant spaces. Remove bag from sprinkler upright in west tenant space. 11/1/2004 12:02:10 PM
|
BLD04-01216
| FIRE-Final Inspection | 10/29/2004 | 11/1/2004 | 11/1/2004 12:00:00 AM | A | FAIL |
|
|
Remove keyed hardware on the interior exit doors and provide sticker on the exterior exit doors. 11/1/2004 12:03:13 PM
|
FIR04-00463
| INSP-Final Inspection | 11/1/2004 | 11/1/2004 | 11/1/2004 12:00:00 AM | A | FAIL |
|
|
Certify backflow preventer and new sprinkler system
|
FIR04-00384
| INSP-Final Inspection | 11/1/2004 | 11/1/2004 | 11/1/2004 12:00:00 AM | A | PASS |
|
|
Underground finaled
|
FIR04-00517
| INSP-Final Inspection | 11/1/2004 | 11/1/2004 | 11/1/2004 12:00:00 AM | P | FAIL |
|
|
Phone line troubles did not go to monitoring station and the duct detectors did not have power
|
FIR04-00484
| INSP-Final Inspection | 11/1/2004 | 11/1/2004 | 11/1/2004 12:00:00 AM | P | FAIL |
|
|
Plan review notes indicate the fire pump is to have 48psi static. Pump only shows 47psi. I will talk to Bill to see if this is a problem tomorrow 11/1/2004 4:25:50 PM
|