Inspections for the day of: Monday, November 1, 2004.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-00558 FIRE-Final Inspection10/29/200411/1/200411/1/2004 12:00:00 AMAFAIL
Need to final fire alarm and fire sprinklers. Verify life safety compiance in all tenant spaces. Remove bag from sprinkler upright in west tenant space. 11/1/2004 12:02:10 PM
BLD04-01216 FIRE-Final Inspection10/29/200411/1/200411/1/2004 12:00:00 AMAFAIL
Remove keyed hardware on the interior exit doors and provide sticker on the exterior exit doors. 11/1/2004 12:03:13 PM
FIR04-00463 INSP-Final Inspection11/1/200411/1/200411/1/2004 12:00:00 AMAFAIL
Certify backflow preventer and new sprinkler system
FIR04-00384 INSP-Final Inspection11/1/200411/1/200411/1/2004 12:00:00 AMAPASS
Underground finaled
FIR04-00517 INSP-Final Inspection11/1/200411/1/200411/1/2004 12:00:00 AMPFAIL
Phone line troubles did not go to monitoring station and the duct detectors did not have power
FIR04-00484 INSP-Final Inspection11/1/200411/1/200411/1/2004 12:00:00 AMPFAIL
Plan review notes indicate the fire pump is to have 48psi static. Pump only shows 47psi. I will talk to Bill to see if this is a problem tomorrow 11/1/2004 4:25:50 PM