Inspections for the day of: Tuesday, November 1, 2005.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02341 Conference11/1/200511/1/200511/1/2005 4:21:39 PMPDONE
earl///please call 30 min prior to meet you; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa reviewed code requirement for move-on house to bring up to code.
ELE05-03956 Rough-In Permanent Service10/31/200511/1/200511/1/2005 4:20:24 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Tina Payne bottom floor only soffits and ceiling parts ok to cover.
ELE05-03960 Temporary Service11/1/200511/1/200511/1/2005 3:40:36 PMPFAIL
ron ###-#### called contr, left corr notice, 408.4 circuit directory shall be provided, 110.12(C) there shall be no broken parts, 250.52(A)(5) electrode shall be minimum 8' long and 5/8" diameter. Fee due.
ELE05-02426 Final11/1/200511/1/200511/1/2005 2:32:29 PMPCANC
###-#### - sanya see ps
ELE05-02898 Final10/31/200511/1/200511/1/2005 1:27:36 PMPPASS
eric-- for 1:30 meeting; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie people moved in, checked all but a few receptacles, ok to final
ELE05-00926 Final11/1/200511/1/200511/1/2005 10:20:24 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr, left survey, 250.8 gnd conductors in lite poles shall use listed connectors, 110.12(A) unused openings shall be closed in boxes in hall and offices, ok to final
ELE05-02876 Final11/1/200511/1/200511/1/2005 10:13:36 AMPCANC
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla Inspection cancelled from web by: Cevyn Recla
ELE05-03948 Rough-In Permanent Service10/31/200511/1/200511/1/2005 9:38:40 AMAPASS
Electrical Rough-in Inspection.; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called to add four rooms and a/c to permit. ric ok, p/s u/g n ok
ELE05-03932 Electrical Rough-In11/1/200511/1/200511/1/2005 9:31:55 AMPCANC
Our Job #05-1327 Unit #198 Cross streets are Emerald and Maple Grove. 8950 W. Emerald. Be aware that there are two units, #198 and #199. Electrician on jobsite is Steve Ruter ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson Inspection cancelled from web by: Kristopher wilson
ELE05-03932 Electrical Rough-In11/1/200511/1/200511/1/2005 9:28:02 AMPCANC
Unit #199 Cross streets are Emerald and Maple Grove. 6980 W. Emerald. Be aware that there are two units, #198 and #199. Electrician on jobsite is Steve Ruter ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson Inspection cancelled from web by: Kristopher wilson
ELE05-03931 Electrical Rough-In11/1/200511/1/200511/1/2005 9:27:52 AMPCANC
Unit #198 Cross streets are Emerald and Maple Grove. 6980 W. Emerald. Be aware that there are two units, #198 and #199. Electrician on jobsite is Steve Ruter ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson Inspection cancelled from web by: Kristopher wilson
ELE05-03931 Electrical Rough-In10/28/200511/1/200511/1/2005 9:07:45 AMANR
Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson met elect, told next time will get reinspection fee.
ELE05-02426 Final10/31/200511/1/200511/1/2005 8:53:58 AMANH
Phone #: ###-#### Internet Inspection Request from: Nikki Day called contr, said to schedule when can get in
ELE05-03472 Permanent Service11/1/200511/1/200511/1/2005 8:47:30 AMPPASS
Scheduled by a contractor via Hello! on 11/1/2005 at 7:37:31 AM. Contact: ###-####. p/s u/g n ok, will final ltr
ELE05-02426 Permanent Service11/1/200511/1/200511/1/2005 12:00:00 AMPPASS
###-#### - sanya house panel, ok to final, p/s, exst meter pak, n, ok