BLD05-03258
| FIRE-Final Inspection | 10/31/2006 | 11/1/2006 | 11/3/2006 11:09:13 AM | A | DEFR |
|
|
No FIR permit or life safety inspection associated with this permit.
|
FIR06-00706
| INSP-Final Inspection | 11/1/2006 | 11/1/2006 | 11/2/2006 1:52:08 PM | P | PART |
|
|
OH fire sprinkler work is good for cover at the drop ceilings.
|
FIR05-00737
| INSP-Final Inspection | 11/1/2006 | 11/1/2006 | 11/1/2006 4:17:21 PM | P | FAIL |
|
|
Missing heat and smoke detectors at the top of the elevator shaft, one duct detector has the wrong sample tube installed, one duct detector is not properly located downstream of all returns, damper above the door to the mech. room is not functioning, tested FACP batteries, phone lines, AC loss, and panel smoke, signals not verified at this time, concluded inspection due to the number of defficiencies, no other items tested.
|
BLD05-01295
| FIRE-Final Inspection | 10/31/2006 | 11/1/2006 | 11/1/2006 4:12:47 PM | P | FAIL |
|
|
Need fire sprinkler and alarm finals prior to BLD life safety final, also noted extinguishers are overdue certification, missing max occupant load sign for the assembly area, missing door closure at mech. room, some items related to fire code review notes are not addressed, instructed contractor to review notes before next inspection.
|
FIR06-00645
| INSP-Alarm Testing | 10/31/2006 | 11/1/2006 | 11/1/2006 3:18:35 PM | P | NR |
|
|
To be rescheduled per contractor as the project is not ready for inspection.
|
BLD05-01971
| BLD-Aging Inspection | 11/1/2006 | 11/1/2006 | 11/1/2006 2:48:16 PM | | DONE |
|
|
Project related fire sprinkler permit is not yet finaled.
|
MIS06-00291
| FIR-Final | 11/1/2006 | 11/1/2006 | 11/1/2006 2:47:23 PM | P | FAIL |
|
|
Need to repair the exit signs at the 1st and 2nd levels of the south office areas, provide a current annual inspection for the existing fire sprinkler system to be completed by a licensed fire sprinkler contractor, need to remove the shrub blocking access to the FDC at the front of the building, remove the padlock and mechanism at the mezzanine bullpen door, remove locking hardware at the egress side to a door directly below an exit sign in the second building.
|
FIR06-00801
| INSP-Final Inspection | 11/1/2006 | 11/1/2006 | 11/1/2006 1:41:07 PM | P | PASS |
|
|
Fire sprinkler work passed field inspection, permit finaled.
|
FIR05-00454
| INSP-Final Inspection | 11/1/2006 | 11/1/2006 | 11/1/2006 1:08:51 PM | P | PASS |
|
|
Per inspection completed by M.Timmerman, fire alarm work is acceptable, inspeciton passed, permit finaled.
|
BLD06-02033
| FIRE-Final Inspection | 11/1/2006 | 11/1/2006 | 11/1/2006 1:07:29 PM | P | PASS |
|
|
Life safety inspection passed.
|
FIR05-00537
| FIR-Aging Inspection | 11/1/2006 | 11/1/2006 | 11/1/2006 12:43:56 PM | | DONE |
|
|
Notified contractor to call for inspection as the work is complete per contractor.
|
FIR06-00437
| INSP-Final Inspection | 10/30/2006 | 11/1/2006 | 11/1/2006 12:39:25 PM | A | NR |
|
|
Not ready for inspection at this time per contractor.
|
FIR06-00136
| INSP-Final Inspection | 10/30/2006 | 11/1/2006 | 11/1/2006 12:38:24 PM | A | PART |
|
|
Per inspection by M. Timmerman the AV portion of work for this permit in the fab level is satisfactory.
|
FIR05-00612
| INSP-Final Inspection | 10/30/2006 | 11/1/2006 | 11/1/2006 12:37:05 PM | A | PART |
|
|
Per inspection by M. Timmerman the AV portion of this work passed inspeciton.
|
BLD06-01044
| FIRE-Final Inspection | 10/30/2006 | 11/1/2006 | 11/1/2006 12:25:38 PM | A | NR |
|
|
The project related fire sprinkler and fire alarm permits must be requested for inspection, approved and finaled prior to BLD life safety final.
|
BLD06-02696
| FIRE-Final Inspection | 11/1/2006 | 11/1/2006 | 11/1/2006 12:01:44 PM | A | FAIL |
|
|
The provided fire extinguishers are overdue the required annual certification.
|
BLD06-02697
| FIRE-Final Inspection | 11/1/2006 | 11/1/2006 | 11/1/2006 12:00:42 PM | A | FAIL |
|
|
The provided fire extinguishers are overdue the required annual certification.
|
MIS06-00278
| FIR-Final | 10/31/2006 | 11/1/2006 | 11/1/2006 11:30:50 AM | A | PASS |
|
|
c/n items have been completed.
|
BLD06-02223
| FIRE-Final Inspection | 10/31/2006 | 11/1/2006 | 11/1/2006 11:11:20 AM | A | PASS |
|
|
Required corrections have been verified for completion, inspection passed.
|
MIS06-00287
| FIR-Final | 10/31/2006 | 11/1/2006 | 11/1/2006 11:00:27 AM | A | FAIL |
|
|
Need to provide current certification tags and lower the mounting height of the fire extinguishers to no higher than 48" AFF, repair and test the emergency lighting throughout the building, if new locksets are installed provide new master key for the Knox Box.
|
FIR06-00545
| INSP-Final Inspection | 10/31/2006 | 11/1/2006 | 10/31/2006 12:02:12 PM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Rob Puckett Inspection cancelled from web by: Rob Puckett
|