Inspections for the day of: Wednesday, November 1, 2006.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-03258 FIRE-Final Inspection10/31/200611/1/200611/3/2006 11:09:13 AMADEFR
No FIR permit or life safety inspection associated with this permit.
FIR06-00706 INSP-Final Inspection11/1/200611/1/200611/2/2006 1:52:08 PMPPART
OH fire sprinkler work is good for cover at the drop ceilings.
FIR05-00737 INSP-Final Inspection11/1/200611/1/200611/1/2006 4:17:21 PMPFAIL
Missing heat and smoke detectors at the top of the elevator shaft, one duct detector has the wrong sample tube installed, one duct detector is not properly located downstream of all returns, damper above the door to the mech. room is not functioning, tested FACP batteries, phone lines, AC loss, and panel smoke, signals not verified at this time, concluded inspection due to the number of defficiencies, no other items tested.
BLD05-01295 FIRE-Final Inspection10/31/200611/1/200611/1/2006 4:12:47 PMPFAIL
Need fire sprinkler and alarm finals prior to BLD life safety final, also noted extinguishers are overdue certification, missing max occupant load sign for the assembly area, missing door closure at mech. room, some items related to fire code review notes are not addressed, instructed contractor to review notes before next inspection.
FIR06-00645 INSP-Alarm Testing10/31/200611/1/200611/1/2006 3:18:35 PMPNR
To be rescheduled per contractor as the project is not ready for inspection.
BLD05-01971 BLD-Aging Inspection11/1/200611/1/200611/1/2006 2:48:16 PM DONE
Project related fire sprinkler permit is not yet finaled.
MIS06-00291 FIR-Final11/1/200611/1/200611/1/2006 2:47:23 PMPFAIL
Need to repair the exit signs at the 1st and 2nd levels of the south office areas, provide a current annual inspection for the existing fire sprinkler system to be completed by a licensed fire sprinkler contractor, need to remove the shrub blocking access to the FDC at the front of the building, remove the padlock and mechanism at the mezzanine bullpen door, remove locking hardware at the egress side to a door directly below an exit sign in the second building.
FIR06-00801 INSP-Final Inspection11/1/200611/1/200611/1/2006 1:41:07 PMPPASS
Fire sprinkler work passed field inspection, permit finaled.
FIR05-00454 INSP-Final Inspection11/1/200611/1/200611/1/2006 1:08:51 PMPPASS
Per inspection completed by M.Timmerman, fire alarm work is acceptable, inspeciton passed, permit finaled.
BLD06-02033 FIRE-Final Inspection11/1/200611/1/200611/1/2006 1:07:29 PMPPASS
Life safety inspection passed.
FIR05-00537 FIR-Aging Inspection11/1/200611/1/200611/1/2006 12:43:56 PM DONE
Notified contractor to call for inspection as the work is complete per contractor.
FIR06-00437 INSP-Final Inspection10/30/200611/1/200611/1/2006 12:39:25 PMANR
Not ready for inspection at this time per contractor.
FIR06-00136 INSP-Final Inspection10/30/200611/1/200611/1/2006 12:38:24 PMAPART
Per inspection by M. Timmerman the AV portion of work for this permit in the fab level is satisfactory.
FIR05-00612 INSP-Final Inspection10/30/200611/1/200611/1/2006 12:37:05 PMAPART
Per inspection by M. Timmerman the AV portion of this work passed inspeciton.
BLD06-01044 FIRE-Final Inspection10/30/200611/1/200611/1/2006 12:25:38 PMANR
The project related fire sprinkler and fire alarm permits must be requested for inspection, approved and finaled prior to BLD life safety final.
BLD06-02696 FIRE-Final Inspection11/1/200611/1/200611/1/2006 12:01:44 PMAFAIL
The provided fire extinguishers are overdue the required annual certification.
BLD06-02697 FIRE-Final Inspection11/1/200611/1/200611/1/2006 12:00:42 PMAFAIL
The provided fire extinguishers are overdue the required annual certification.
MIS06-00278 FIR-Final10/31/200611/1/200611/1/2006 11:30:50 AMAPASS
c/n items have been completed.
BLD06-02223 FIRE-Final Inspection10/31/200611/1/200611/1/2006 11:11:20 AMAPASS
Required corrections have been verified for completion, inspection passed.
MIS06-00287 FIR-Final10/31/200611/1/200611/1/2006 11:00:27 AMAFAIL
Need to provide current certification tags and lower the mounting height of the fire extinguishers to no higher than 48" AFF, repair and test the emergency lighting throughout the building, if new locksets are installed provide new master key for the Knox Box.
FIR06-00545 INSP-Final Inspection10/31/200611/1/200610/31/2006 12:02:12 PMACANC
Phone #: ###-#### Internet Inspection Request from: Rob Puckett Inspection cancelled from web by: Rob Puckett