ELE10-02226
| Final | 11/1/2010 | 11/1/2010 | 11/1/2010 12:39:11 PM | P | PART |
|
|
steve Phone #: ###-#### NEC 210.62 Show windows receptacles, one receptacle is required for every 12 linear feet. BCC NEC 110.16 Office furniture shall be installed per manufacture instructions NOTE corrections shall be made within 5 days.
|
ELE10-02401
| Permanent Service | 11/1/2010 | 11/1/2010 | 11/1/2010 11:17:21 AM | A | CANC |
|
|
call steve sellers for access Phone #: ###-#### >> Inspection requested via web by steve sellers NEC 110.26 workspace shall be provided . NEC 230.2 shall be supplied by only one service,need to meet the requirement of article 230. NOTE corrections shall be made within 5 days or further actions shall be taken- Removal of power.
|
ELE10-01361
| Electrical Rough-In | 10/31/2010 | 11/1/2010 | 11/1/2010 9:46:40 AM | A | PASS |
|
|
Bathroom floorheat Phone #: ###-#### >> Inspection requested via web by Jim Williams floor heat ok to cover
|
ELE10-02376
| Rough-In Permanent Service | 10/30/2010 | 11/1/2010 | 11/1/2010 9:06:11 AM | A | PASS |
|
|
Call Dino with any questions. Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser ri ps ug new ok
|
ELE09-00567
| Final | 10/27/2010 | 11/1/2010 | 11/1/2010 8:20:04 AM | A | PASS |
|
|
Warren Phone #: ###-#### ok final
|