Inspections for the day of: Monday, November 1, 2010.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02226 Final11/1/201011/1/201011/1/2010 12:39:11 PMPPART
steve Phone #: ###-#### NEC 210.62 Show windows receptacles, one receptacle is required for every 12 linear feet. BCC NEC 110.16 Office furniture shall be installed per manufacture instructions NOTE corrections shall be made within 5 days.
ELE10-02401 Permanent Service11/1/201011/1/201011/1/2010 11:17:21 AMACANC
call steve sellers for access Phone #: ###-#### >> Inspection requested via web by steve sellers NEC 110.26 workspace shall be provided . NEC 230.2 shall be supplied by only one service,need to meet the requirement of article 230. NOTE corrections shall be made within 5 days or further actions shall be taken- Removal of power.
ELE10-01361 Electrical Rough-In10/31/201011/1/201011/1/2010 9:46:40 AMAPASS
Bathroom floorheat Phone #: ###-#### >> Inspection requested via web by Jim Williams floor heat ok to cover
ELE10-02376 Rough-In Permanent Service10/30/201011/1/201011/1/2010 9:06:11 AMAPASS
Call Dino with any questions.
Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser ri ps ug new ok
ELE09-00567 Final10/27/201011/1/201011/1/2010 8:20:04 AMAPASS
Warren Phone #: ###-#### ok final