Inspections for the day of: Friday, November 1, 2013.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02968 Permanent Service11/1/201311/1/201311/1/2013 2:11:19 PMPPASS
Krista Phone #: ###-#### p/s u/g n ok
ELE13-03020 Rough-In Permanent Service10/30/201311/1/201311/1/2013 1:32:33 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Alan Lusk ri ok, p/s u/g n ok
ELE13-02990 Rough-In Permanent Service10/31/201311/1/201311/1/2013 12:53:23 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
ELE13-02070 Final11/1/201311/1/201311/1/2013 12:16:54 PMPPASS
Mucho Phone #: ###-#### ok final
ELE08-02423 ELE-Aging Inspection11/1/201311/1/201311/1/2013 10:19:25 AM DONE
still under construction until units completed
ELE13-03046 Final10/31/201311/1/201311/1/2013 10:17:30 AMAPASS
Ran a new 20amp 120v circuit #32 from panel CHA1, to a new duplex receptacle on top of the gondola on isle 34 above the Fresh Pet refrigerators.

Thanks, Dan Phone #: ###-#### >> Inspection requested via web by Dan Mitchell ok final
ELE13-03046 Electrical Rough-In10/31/201311/1/201311/1/2013 10:11:34 AMAPASS
Ran a new 20amp 120v circuit #32 from panel CHA1, to a new duplex receptacle on top of the gondola on isle 34 above the Fresh Pet refrigerators.

Thanks, Dan Phone #: ###-#### >> Inspection requested via web by Dan Mitchell ri ok
ELE13-03045 Final10/31/201311/1/201311/1/2013 9:57:25 AMAPART
Please call prior to arrival. Phone #: ###-#### >> Inspection requested via web by Daniel Schaffeld called, contractor shall label breaker at panel and find listing for warmer, shall provide gfci breaker in panel for warmer per NEC 422.51, will fix and recall
ELE13-02517 Final10/31/201311/1/201311/1/2013 9:12:19 AMAPASS
Stephanie Phone #: ###-#### ok final
ELE13-03050 Temporary Service10/31/201311/1/201311/1/2013 9:06:07 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman t/s o/h n ok
ELE13-02261 Final10/31/201311/1/201311/1/2013 8:16:46 AMAPASS
Lock box combo 8072 Phone #: ###-#### >> Inspection requested via web by Clay Morgan corrections made, ok final