Inspections for the day of: Wednesday, November 1, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03678 Electrical Rough-In11/1/201711/1/201711/1/2017 2:19:06 PMPPASS
David Joseph ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
Wall rough in ok cover
ELE17-01826 Permanent Service11/1/201711/1/201711/1/2017 2:01:26 PMPPASS
Service change out back in alley Phone #: ###-#### Inspection requested via web by John VanZandt
p/s u/g n ok
ELE17-03473 Electrical Rough-In11/1/201711/1/201711/1/2017 1:30:48 PMPPASS
Finish rough-in inspection for basement Phone #: ###-#### Inspection requested via web by Kevin Perez
Basement rough in ok cover
ELE17-03682 Electrical Rough-In10/31/201711/1/201711/1/2017 10:53:07 AMAPASS
call for access Phone #: ###-#### Inspection requested via web by steve sellers
5' Pony wall rough in ok cover
ELE17-03664 Final10/31/201711/1/201711/1/2017 10:19:50 AMAFAIL
This Project Is Done And Ready For Inspection Please Call With Any Questions Or Concerns Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett
352.10(F)- Informational note sch 80 shall be used where subject to physical damage. Where emerging from grade under 50 amp RV receptacle sch. 40 installed.
ELE17-03664 Electrical Rough-In11/1/201711/1/201711/1/2017 10:16:43 AMPPASS
This Project Is Done And Ready For Inspection Please Call With Any Questions Or Concerns Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett
Underground rough in ok cover.
ELE17-03453 Final10/31/201711/1/201711/1/2017 9:17:15 AMAFAIL
There is a lock box at the bottom of the stairs, attached to the railing. The code is 012. Phone #: ###-#### Inspection requested via web by Barbara Szurgot
210.8(B)- All 120 volt receptacle outlets installed with in 6' of a sink shall have GFCI protection.
As per print shall comply with 2012 IBC.
2012 International Energy Concervation Code C405.2.2.2- Occupancy sensors shall be installed in all meeting rooms, break room areas, private offices and other areas 300 sq. ft or less. After 30 minutes or less shut off setting. All areas shall have occ sensors installed.
ELE17-03453 Final10/31/201711/1/201710/31/2017 4:09:11 PMACANC
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot Inspection cancelled from web by: Barbara Szurgot