Inspections for the day of: Wednesday, November 1, 2017.
Number of inspections: 24
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDan Ediger
TitlePLM-INSPECTOR
Phone #869-5166
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM17-01296 PLM-Aging Inspection11/1/201711/1/201711/2/2017 4:40:20 PM PASS
PLM17-04281 Plumbing Rough-in11/1/201711/1/201711/1/2017 4:13:08 PMPPASS
Phone #: ###-#### Inspection requested via web by Brandon Rohricht
PLM17-03043 Final11/1/201711/1/201711/1/2017 4:04:26 PMPPASS
PLM17-04288 Other11/1/201711/1/201711/1/2017 4:02:04 PMPPASS
Call when you are on your way- Britton Phone #: ###-####. conference
PLM17-04206 Final11/1/201711/1/201711/1/2017 3:35:16 PMPPASS
Please call John Artega at ###-#### prior to inspection Phone #: ###-#### Inspection requested via web by Mary LaFayette
PLM17-04289 Groundwork11/1/201711/1/201711/1/2017 3:09:17 PMPFAIL
Phone #: ###-#### Inspection requested via web by Brian Johansen. Wrong address
PLM17-04290 Groundwork11/1/201711/1/201711/1/2017 3:08:49 PMPFAIL
Phone #: ###-#### Inspection requested via web by Brian Johansen. Wrong permit
PLM17-04291 Groundwork11/1/201711/1/201711/1/2017 3:08:12 PMPFAIL
Phone #: ###-#### Inspection requested via web by Brian Johansen.
Wrong permit
PLM17-03043 Final11/1/201711/1/201711/1/2017 2:30:22 PMPFAIL
Phone #: ###-#### Inspection requested via web by Jason Adams.
Pipe the RP air gap drain 1", full size to the outdoors. It is reduced to 1/2"
PLM16-04144 Plumbing Rough-in10/31/201711/1/201711/1/2017 2:30:22 PMPPART
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER. MOB room dwv pressure test for wall plumbing .
PLM17-04141 Final10/31/201711/1/201711/1/2017 1:26:54 PMPPART
Please contact technician Jim Reed at ###-#### prior to arrival. Phone #: ###-#### Inspection requested via web by Andrea Grigsby.
OK to cover. PRV needs to be certified
PLM17-04280 Water and/or Sewer11/1/201711/1/201711/1/2017 1:15:38 PMPPART
Phone #: ###-#### Inspection requested via web by Darren Wood.
This permit is only for 7215. You need to pull a seperate permit for 7217.
PLM17-03952 Groundwork11/1/201711/1/201711/1/2017 12:47:56 PMPPASS
All piping in the concrete must be protecded. Wrap prior to pourning concrete
PLM17-03513 Groundwork11/1/201711/1/201711/1/2017 12:33:49 PMPPART
Please bring your pressure testing equipment. Thanks! Phone #: ###-#### Inspection requested via web by Seth Olsen.
Water service ok.
Use drainage fittings on the 2" pressure line.
PLM17-04161 Water and/or Sewer11/1/201711/1/201711/1/2017 12:05:16 PMPPART
Phone #: ###-#### Inspection requested via web by Katherine Creekbaum.
The tank passed the 24hr test. Sewer held test and can be backfilled.
The 3" grease int. vent needs ran and tested prior to backfill of the vent.
PLM17-04138 Final11/1/201711/1/201711/1/2017 11:33:38 AMAPASS
PLM17-04138 Final10/31/201711/1/201711/1/2017 10:24:25 AMANH
Please contact Jean at ###-####. Phone #: ###-#### Inspection requested via web by Andrea Grigsby. tagged
PLM17-04165 Water Heater Final11/1/201711/1/201711/1/2017 10:11:52 AMACANC
1st ###-####
PLM17-04165 Final10/31/201711/1/201711/1/2017 10:09:30 AMACANC
Please call homeowner for access - this is a rental ; no tenant.
customer said he can only do this before 9:00 a.m. any day.
Please call him if this won''t work Phone #: ###-#### Inspection requested via web by Aaron Alandt
PLM17-03427 Final10/31/201711/1/201711/1/2017 10:07:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Brian Johansen
PLM17-01257 DOC - Permit Finaled11/1/201711/1/201711/1/2017 9:40:14 AMPPASS
PLM16-01473 PLM-Aging Inspection11/1/201711/1/201711/1/2017 9:09:41 AM PEND
PLM17-04209 Water and/or Sewer10/31/201711/1/201711/1/2017 9:07:30 AMAPART
Sewer Line ; connection to grease interceptor - See Brandon Dibble, T.A. Dibble Excavation, Superintendent onsite Phone #: ###-#### Inspection requested via web by Betty Dibble.
Start the grease interceptor 24hr test
PLM17-04280 Water and/or Sewer11/1/201711/1/201711/1/2017 8:30:39 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darren Wood.
Sewer on the west end failed pressure test. all else ok to cover.
Need final sewer and water connections inspected upon completion.