MEC19-04916
| Final | 10/31/2019 | 11/1/2019 | 11/1/2019 3:53:28 PM | P | PASS |
|
|
INSTALLER DUSTIN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
|
MEC19-04919
| Final | 10/31/2019 | 11/1/2019 | 11/1/2019 3:19:16 PM | P | PASS |
|
|
Please call Craig on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co locking caps ok
|
MEC19-04603
| Final | 10/30/2019 | 11/1/2019 | 11/1/2019 2:25:03 PM | P | PASS |
|
|
Please call Kyle to ensure install is complete. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg- furnace a/c coil mini split locking caps ok
|
MEC19-04603
| Pressure Test | 10/30/2019 | 11/1/2019 | 11/1/2019 2:22:04 PM | P | CANC |
|
|
Please call Kyle to ensure install is complete. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg- flue test not needed
|
MEC19-04909
| Final | 10/31/2019 | 11/1/2019 | 11/1/2019 1:22:29 PM | P | PASS |
|
|
ladder is behind vinyl fence out by the patio Phone #: ###-#### Inspection requested via web by Aaron Toomey- RTU final ok
|
MEC19-04824
| Final | 10/31/2019 | 11/1/2019 | 11/1/2019 12:40:28 PM | P | CANC |
|
|
Please call Dave on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- per phone call with Dave will reschedule for another day
|
MEC19-03919
| Final | 10/31/2019 | 11/1/2019 | 11/1/2019 12:10:04 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by jamie berg- a/c coil gas piping ok
|
MEC19-03918
| Final | 10/31/2019 | 11/1/2019 | 11/1/2019 12:09:24 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by jamie berg- a/c gas piping ok
|
MEC19-02727
| Final | 10/31/2019 | 11/1/2019 | 11/1/2019 11:02:47 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek- per phone call with Jeff- missing air balance- will reschedule
|
MEC19-04793
| Final | 11/1/2019 | 11/1/2019 | 11/1/2019 10:50:34 AM | A | PASS |
|
|
furnace only in crawl co ok
|
MEC19-04849
| Rough-in | 10/31/2019 | 11/1/2019 | 11/1/2019 9:15:07 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kristy Watson- R/I ok- need to support crawl supply duct off ground at crawl entrance by final and seal dryer duct to termination box by final - talked to Kristy about this
|
MEC19-04849
| Pressure Test | 11/1/2019 | 11/1/2019 | 11/1/2019 9:13:32 AM | A | PASS |
|
|
20lb gas pass tagged meter location
|
MEC19-03569
| Final | 11/1/2019 | 11/1/2019 | 11/1/2019 8:54:57 AM | A | PASS |
|
|
fireplace final ok
|
MEC19-03602
| Final | 10/31/2019 | 11/1/2019 | 11/1/2019 8:54:07 AM | A | PASS |
|
|
GARAGE CODE 0801 Phone #: ###-#### Inspection requested via web by Aaron Alandt- final ok- locking caps installed
|
MEC18-05980
| Mec-Aging Inspection | 11/1/2019 | 11/1/2019 | 11/1/2019 7:43:51 AM | | CANC |
|
|
|
MEC18-05980
| DOC - Permit Expired | 11/1/2019 | 11/1/2019 | 11/1/2019 7:43:46 AM | A | PASS |
|
|
no calls- no activity
|
MEC18-04340
| Mec-Aging Inspection | 11/1/2019 | 11/1/2019 | 11/1/2019 7:42:59 AM | | FAIL |
|
|
needs called in for final or request extension on permit
|