FIR03-00600
| INSP-Supply line flush | 11/7/2003 | 11/10/2003 | 11/10/2003 12:00:00 AM | A | PASS |
|
|
underground flush is ok 11/10/2003 9:12:59 AM
|
FIR03-00555
| INSP-Supply line flush | 11/7/2003 | 11/10/2003 | 11/10/2003 12:00:00 AM | A | PASS |
|
|
underground flush is ok 11/10/2003 9:13:09 AM
|
FIR03-00555
| INSP-Sprinkler Rough-in/Hydro | 11/7/2003 | 11/10/2003 | 11/10/2003 12:00:00 AM | A | FAIL |
|
|
Measuring off of wall in anti-freeze area the upright sprinkler heads are over spaced, closet is missing sprinkler protection 11/10/2003 9:11:59 AM
|
BLD03-00657
| FIRE-Final Inspection | 11/7/2003 | 11/10/2003 | 11/10/2003 12:00:00 AM | A | PART |
|
|
temp occ --gary; Phone #: ###-#### Temp occupancy given until the fire alarm system has been approved, installed and tested per Dave Millers permission 11/10/2003 9:45:05 AM
|
FIR03-00600
| INSP-Sprinkler Rough-in/Hydro | 11/7/2003 | 11/10/2003 | 11/10/2003 12:00:00 AM | A | PASS |
|
|
piping is ok to cover but one pendant head in the entry lobby is painted 11/10/2003 9:12:36 AM
|
FIR03-00576
| INSP-Final Inspection | 11/7/2003 | 11/10/2003 | 11/10/2003 12:00:00 AM | A | FAIL |
|
|
can't give final until the ceiling tile is in. Piping is ok to cover 11/10/2003 10:59:02 AM
|
FIR03-00644
| INSP-Final Inspection | 11/7/2003 | 11/10/2003 | 11/10/2003 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/7/2003 at 2:50:27 PM. Contact: ###-####.
|
BLD03-01977
| FIRE-Conference | 11/7/2003 | 11/10/2003 | 11/10/2003 12:00:00 AM | A | FAIL |
|
|
provide the emergency light in the exit corridor and occupant load sign. Project still needs the fire alarm system approved. No temp occupancy was given due to the items above and no fire alarm plans have been submitted at this time 11/10/2003 10:20:38 AM
|
BLD03-01300
| FIRE-Final Inspection | 11/7/2003 | 11/10/2003 | 11/10/2003 12:00:00 AM | A | PASS |
|
|
life safety finaled 11/10/2003 1:28:21 PM
|
MIS03-00225
| FIR-Final | 11/7/2003 | 11/10/2003 | 11/10/2003 12:00:00 AM | A | FAIL |
|
|
###-#### brian Provide fire extinguisher mounted at 48" with current inspection tag and provide permanent suite number for the space 11/10/2003 12:27:29 PM
|
FIR03-00375
| INSP-Final Inspection | 11/10/2003 | 11/10/2003 | 11/10/2003 12:00:00 AM | A | PART |
|
|
Temp occupancy given until the fire alarm system has been approved, installed and tested per Dave Millers permission
|
FIR03-00658
| INSP-Final Inspection | 11/10/2003 | 11/10/2003 | 11/10/2003 12:00:00 AM | A | PART |
|
|
Temp occupancy given until the fire alarm system has been approved, installed and tested per Dave Millers permission
|
FIR03-00585
| INSP-Sprinkler Rough-in/Hydro | 11/10/2003 | 11/10/2003 | 11/10/2003 12:00:00 AM | P | PASS |
|
|
sprinkler piping is ok to cover 11/10/2003 4:26:46 PM
|