Inspections for the day of: Wednesday, November 10, 2004.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00479 INSP-Alarm Testing11/9/200411/10/200411/10/2004 12:00:00 AMPFAIL
The only two items tested are the battery calcs and the phone lines. Both items ok. Started to test sprinkler devices but they did not report to panel. Failed and stopped inspection 11/10/2004 3:27:29 PM
BLD04-01268 FIRE-Final Inspection11/10/200411/10/200411/10/2004 12:00:00 AMPPART
A temporary occupancy was given with dave millers permission until the hardware issues on the pocket doors has been addressed. Doors have been removed for now 11/10/2004 1:33:49 PM
FIR04-00545 INSP-Final Inspection11/10/200411/10/200411/10/2004 12:00:00 AMPPASS
Fire sprinklers finaled
FIR04-00539 INSP-Final Inspection11/10/200411/10/200411/10/2004 12:00:00 AMPPASS
Fire alarms finaled