ESC09-00573
| Complaint Inspection | 11/10/2009 | 11/10/2009 | 11/10/2009 4:13:17 PM | P | CANC |
|
|
wrong type inspection entered, supposed to be general
|
ESC09-00573
| General Inspection | 11/10/2009 | 11/10/2009 | 11/10/2009 4:12:54 PM | P | PART |
|
|
talked to electrical contractor, to put up address, told to talk with general about signs and address to be posted
|
ESC09-00613
| General Inspection | 11/10/2009 | 11/10/2009 | 11/10/2009 4:09:28 PM | P | PASS |
|
|
looked ok
|
ESC09-00593
| General Inspection | 11/10/2009 | 11/10/2009 | 11/10/2009 4:08:30 PM | P | PASS |
|
|
looked ok
|
ELE09-02191
| Electrical Rough-In | 11/10/2009 | 11/10/2009 | 11/10/2009 4:07:47 PM | P | PASS |
|
|
gene - uffer ground inspection Phone #: ###-#### ok to pour concrete encased electrode
|
ESC09-00691
| General Inspection | 11/10/2009 | 11/10/2009 | 11/10/2009 3:37:06 PM | P | PASS |
|
|
looked ok
|
ESC09-00316
| General Inspection | 11/10/2009 | 11/10/2009 | 11/10/2009 3:31:32 PM | P | PASS |
|
|
looked ok
|
ELE09-02163
| Final | 11/9/2009 | 11/10/2009 | 11/10/2009 3:30:54 PM | P | CANC |
|
|
bonding & underground inspection for the pm Phone #: ###-#### Internet Inspection Request from: Jari Rivers wrong type request, see ri
|
ELE09-02163
| Electrical Rough-In | 11/10/2009 | 11/10/2009 | 11/10/2009 3:30:38 PM | P | PART |
|
|
bonding & underground inspection for the pm Phone #: ###-#### Internet Inspection Request from: Jari Rivers pool bonding and u/g only ok to cover
|
ESC09-00445
| General Inspection | 11/10/2009 | 11/10/2009 | 11/10/2009 3:28:38 PM | P | PASS |
|
|
looked ok
|
ELE09-02185
| Conference | 11/10/2009 | 11/10/2009 | 11/10/2009 2:57:30 PM | P | DONE |
|
|
Met contractor,talked about service, transformer, service disconnect overcurrent protection, grounding, flex conduit, electric discharge lighting plugs,
|
ELE09-02194
| Rough-In Permanent Service | 11/10/2009 | 11/10/2009 | 11/10/2009 2:52:15 PM | P | PASS |
|
|
Darren ###-#### ric ok, p/s u/g n ok
|
ELE09-02185
| Rough-In Permanent Service | 11/9/2009 | 11/10/2009 | 11/10/2009 2:02:02 PM | P | CANC |
|
|
please call so cory can meet inspector out there if possible with eta Phone #: ###-#### Internet Inspection Request from: cory carman see conference
|
ELE09-02188
| Electrical Rough-In | 11/10/2009 | 11/10/2009 | 11/10/2009 12:40:40 PM | P | FAIL |
|
|
jim Phone #: ###-#### called left correction notice, NEC 300.14 shall provide 6" free conductor length, 330.30(B) shall secure mc cable within 12" of box, 300.4(A)&(D) edge of hole and edge of cable shall be 1 1/4" from edge of framing member BCC shall not secure wiring in valley of framing member, metal studs, shall make corrections within 2 weeks
|
ELE09-02159
| Final | 11/9/2009 | 11/10/2009 | 11/10/2009 10:39:25 AM | A | CANC |
|
|
PO# 110833 Ran a new 20 A circuit for bathroom, put entire bathroom on circuit, lights and GFCI, Please call Brian @ ###-#### when you are on your way, thank you. Phone #: ###-#### Internet Inspection Request from: Dan Mitchell called contractor, owner out of town, contractor could not meet, asked to reschedule for when somebody will be home, no esc this project
|
ELE09-02052
| Electrical Rough-In | 11/9/2009 | 11/10/2009 | 11/10/2009 10:37:35 AM | A | PASS |
|
|
ufer inspection please call before to ensure access Phone #: ###-#### Internet Inspection Request from: Bruce Herold ok to pour concrete encased electrode anop, no esc this project
|
ELE09-02186
| Temporary Service | 11/9/2009 | 11/10/2009 | 11/10/2009 10:10:30 AM | A | PASS |
|
|
steve Phone #: ###-#### called, t/s u/g n ok
|
ELE09-01685
| Final | 11/9/2009 | 11/10/2009 | 11/10/2009 9:24:01 AM | A | PASS |
|
|
Any questions please call,garage code 1234 or 4321, thanks! TW. Phone #: ###-#### Internet Inspection Request from: Stephen Kren ok to final
|
ELE09-02147
| Electrical Rough-In | 11/9/2009 | 11/10/2009 | 11/10/2009 8:41:17 AM | A | PASS |
|
|
replaced unsafe wires going to kitchen recep Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ric ok, see final, no esc this project
|
ELE09-02147
| Final | 11/10/2009 | 11/10/2009 | 11/10/2009 8:40:26 AM | A | PASS |
|
|
replaced unsafe wires going to kitchen recep Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final, no esc this project
|
ELE09-01799
| Final | 11/10/2009 | 11/10/2009 | 11/10/2009 8:31:48 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams called, ok to final, no esc this project, signed structural card
|