Inspections for the day of: Tuesday, November 10, 2009.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC09-00573 Complaint Inspection11/10/200911/10/200911/10/2009 4:13:17 PMPCANC
wrong type inspection entered, supposed to be general
ESC09-00573 General Inspection11/10/200911/10/200911/10/2009 4:12:54 PMPPART
talked to electrical contractor, to put up address, told to talk with general about signs and address to be posted
ESC09-00613 General Inspection11/10/200911/10/200911/10/2009 4:09:28 PMPPASS
looked ok
ESC09-00593 General Inspection11/10/200911/10/200911/10/2009 4:08:30 PMPPASS
looked ok
ELE09-02191 Electrical Rough-In11/10/200911/10/200911/10/2009 4:07:47 PMPPASS
gene - uffer ground inspection Phone #: ###-#### ok to pour concrete encased electrode
ESC09-00691 General Inspection11/10/200911/10/200911/10/2009 3:37:06 PMPPASS
looked ok
ESC09-00316 General Inspection11/10/200911/10/200911/10/2009 3:31:32 PMPPASS
looked ok
ELE09-02163 Final11/9/200911/10/200911/10/2009 3:30:54 PMPCANC
bonding & underground inspection for the pm Phone #: ###-#### Internet Inspection Request from: Jari Rivers wrong type request, see ri
ELE09-02163 Electrical Rough-In11/10/200911/10/200911/10/2009 3:30:38 PMPPART
bonding & underground inspection for the pm Phone #: ###-#### Internet Inspection Request from: Jari Rivers pool bonding and u/g only ok to cover
ESC09-00445 General Inspection11/10/200911/10/200911/10/2009 3:28:38 PMPPASS
looked ok
ELE09-02185 Conference11/10/200911/10/200911/10/2009 2:57:30 PMPDONE
Met contractor,talked about service, transformer, service disconnect overcurrent protection, grounding, flex conduit, electric discharge lighting plugs,
ELE09-02194 Rough-In Permanent Service11/10/200911/10/200911/10/2009 2:52:15 PMPPASS
Darren ###-#### ric ok, p/s u/g n ok
ELE09-02185 Rough-In Permanent Service11/9/200911/10/200911/10/2009 2:02:02 PMPCANC
please call so cory can meet inspector out there if possible with eta Phone #: ###-#### Internet Inspection Request from: cory carman see conference
ELE09-02188 Electrical Rough-In11/10/200911/10/200911/10/2009 12:40:40 PMPFAIL
jim Phone #: ###-#### called left correction notice, NEC 300.14 shall provide 6" free conductor length, 330.30(B) shall secure mc cable within 12" of box, 300.4(A)&(D) edge of hole and edge of cable shall be 1 1/4" from edge of framing member BCC shall not secure wiring in valley of framing member, metal studs, shall make corrections within 2 weeks
ELE09-02159 Final11/9/200911/10/200911/10/2009 10:39:25 AMACANC
PO# 110833 Ran a new 20 A circuit for bathroom, put entire bathroom on circuit, lights and GFCI, Please call Brian @ ###-#### when you are on your way, thank you. Phone #: ###-#### Internet Inspection Request from: Dan Mitchell called contractor, owner out of town, contractor could not meet, asked to reschedule for when somebody will be home, no esc this project
ELE09-02052 Electrical Rough-In11/9/200911/10/200911/10/2009 10:37:35 AMAPASS
ufer inspection
please call before to ensure access Phone #: ###-#### Internet Inspection Request from: Bruce Herold ok to pour concrete encased electrode anop, no esc this project
ELE09-02186 Temporary Service11/9/200911/10/200911/10/2009 10:10:30 AMAPASS
steve Phone #: ###-#### called, t/s u/g n ok
ELE09-01685 Final11/9/200911/10/200911/10/2009 9:24:01 AMAPASS
Any questions please call,garage code 1234 or 4321, thanks! TW. Phone #: ###-#### Internet Inspection Request from: Stephen Kren ok to final
ELE09-02147 Electrical Rough-In11/9/200911/10/200911/10/2009 8:41:17 AMAPASS
replaced unsafe wires going to kitchen recep Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ric ok, see final, no esc this project
ELE09-02147 Final11/10/200911/10/200911/10/2009 8:40:26 AMAPASS
replaced unsafe wires going to kitchen recep Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final, no esc this project
ELE09-01799 Final11/10/200911/10/200911/10/2009 8:31:48 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Jim Williams called, ok to final, no esc this project, signed structural card