BLD09-01339
| FIRE-Conference | 11/10/2009 | 11/10/2009 | 11/10/2009 3:27:12 PM | P | DONE |
|
|
I went over life safety requirements with Chris Beutter. As verified with the plan reviewer the exit signs are required to have battery backup.
|
FIR09-00408
| INSP-Sprinkler Rough-in/Hydro | 11/10/2009 | 11/10/2009 | 11/10/2009 3:12:15 PM | P | PART |
|
|
The underground hydro test passed. The two overhead hydro tests failed.
|
BLD09-01685
| FIRE-Final Inspection | 11/10/2009 | 11/10/2009 | 11/10/2009 2:44:11 PM | P | FAIL |
|
|
Todays inspection was actually for a conference. The insulation at the deck has been repaired and the ceiling tile can be installed pending other trade inspections.
|
BLD09-01982
| FIRE-Final Inspection | 11/9/2009 | 11/10/2009 | 11/10/2009 2:42:34 PM | A | FAIL |
|
|
See the city approved plans for a list of deficiencies which include providing testing/verification of the smoke evac system, provide emergency lighting in the main sales floor area, repair the existing emergency lighting in the rear exit corridor and mount the fire extinguisher and provide a current inspection tag.
|
FIR09-00609
| INSP-Final Inspection | 11/10/2009 | 11/10/2009 | 11/10/2009 1:44:36 PM | P | PASS |
|
|
Permit finaled
|
FIR09-00571
| INSP-Final Inspection | 11/10/2009 | 11/10/2009 | 11/10/2009 1:28:56 PM | P | PASS |
|
|
Permit finaled
|