Inspections for the day of: Tuesday, November 10, 2015.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-02123 ELE-Aging Inspection11/10/201511/10/201511/12/2015 7:46:39 AM DONE
Still under construction
ELE15-03396 Electrical Rough-In11/10/201511/10/201511/10/2015 3:04:14 PMPPASS
We need an underground inspection. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker
Slab A only rough in ok cover
ELE15-03389 Permanent Service11/10/201511/10/201511/10/2015 2:17:36 PMPFAIL
This is the Lamar Bill board sign located at the referenced address. The inspection request is for permanent service. If no defects please final. Phone #: ###-#### Inspection requested via web by David Mackey
110.24- Available fault current shall be post with the date calculated prior to permanent service inspection.
408.4- Circuit directory shall be complete for final.
ELE15-03590 Rough-In Permanent Service11/10/201511/10/201511/10/2015 2:17:16 PMPPASS
Rough in ok cover p/s u/g n ok
ELE15-03476 Final11/9/201511/10/201511/10/2015 1:32:10 PMPPASS
Phone #: ###-#### Inspection requested via web by Ryan Wake Final ok
ELE15-03651 Rough-In Permanent Service11/10/201511/10/201511/10/2015 1:12:53 PMPPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok
ELE15-03550 Conference11/10/201511/10/201511/10/2015 12:44:46 PMPDONE
John Phone #: ###-#### Discussed minimum required for final inspection due to budget issues. New contractor taking over job. Other permit ELE14-00804. Explained 1 outlet in habitable areas to be switched at door locations other to be blanked, and cook top and under stubs shall not have exposed wiring at time of final.
ELE15-03406 Electrical Rough-In11/9/201511/10/201511/10/2015 11:12:23 AMAPASS
Jesse Phone #: ###-####
1" EMT and #6 bare ground only from roof to solar disconnect rough in ok cover
ELE15-03298 Electrical Rough-In11/10/201511/10/201511/10/2015 10:25:58 AMAPASS
This House Is Ready For A Rough In Inspection For Cover The Door Is Open And Call With Any Questions Or Concerns Please! Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett House rewire rough in ok cover
ELE15-03634 Electrical Rough-In11/9/201511/10/201511/10/2015 9:52:33 AMAPASS
If door is locked call for key code Phone #: ###-#### Inspection requested via web by Kyle Lott Bathroom rough in ok cover
ELE15-01792 Final11/9/201511/10/201511/10/2015 9:17:50 AMAFAIL
Ken Phone #: ###-####
300.5- Underground to sign shall be minimum of 18" deep to conduit. No other open permits exist on this address. Sign contractor to check and call back.
ELE15-03514 Electrical Rough-In11/9/201511/10/201511/10/2015 8:37:45 AMAPASS
We are requesting a rough-in inspection for tomorrow 11/10/15 - 1st thing in the morning if possible. Our contact is Bryant @ ###-####. Thank you,
Phone #: ###-#### Inspection requested via web by Clint Tate All walls and hard lids rough in ok cover