BLD05-01282
| FIRE-Conference | 10/28/2015 | 11/4/2015 | | A | |
|
|
follow up
|
BLD15-03223
| FIRE-Final Inspection | 11/10/2015 | 11/10/2015 | 11/10/2015 3:20:48 PM | P | FAIL |
|
|
Repair all exit signs and emergency lights, provide emergency lighting ina all paths of travel. Fire sprinkler coverage is missing in several rooms and possibly blocked in another with painted sprinkler heads. Sprinkler contractor to provide modifications. Install all ceiling tile. Provide verification that the fire alarm system is being monitored. Fire alarm system notification is missing in many areas and overspaced in others. Fire alarm contractor to provide modifications. Provide single action hardware for all exterior doors. Remove dead bolts from exterior doors. All access controlled egress doors to meet IFC 1008.1.9.8 or 1008.1.9.9. Provide fire extinguishers on mezzanines. The wall layout/mezzanines are not shown on the plans/does not match plans. Please verify with building plan reviewer.
I suggested to the contractor that a fire sprinkler contractor and a fire alarm contractor walk the building and provide code compliant systems.
|
BLD15-01983
| FIRE-Final Inspection | 11/9/2015 | 11/10/2015 | 11/10/2015 3:14:25 PM | P | FAIL |
|
|
provide smoke evac testing, provide "clouds" around the lower pendant sprinkler heads.
|
FIR15-00555
| INSP-Sprinkler Rough-in | 11/10/2015 | 11/10/2015 | 11/10/2015 3:06:11 PM | P | PASS |
|
|
underground supply line is ok for cover
|
FIR15-00573
| INSP-Final Inspection | 11/9/2015 | 11/10/2015 | 11/10/2015 11:31:29 AM | P | PASS |
|
|
permit finaled
|
FIR15-00382
| INSP-Final Inspection | 11/5/2015 | 11/10/2015 | 11/10/2015 9:46:24 AM | A | FAIL |
|
|
Provide Document Box, provide testing forms, provide map, provide correct batteries, provide knox box, plans show ion detectors but none are existing or installed. No actual testing was performed and plan mods may be needed.
|
BLD15-03430
| FIRE-Final Inspection | 11/10/2015 | 11/10/2015 | 11/10/2015 8:34:00 AM | P | PASS |
|
|
life safety passed
|
FIR15-00756
| INSP-Final Inspection | 11/9/2015 | 11/10/2015 | 11/9/2015 1:43:50 PM | A | PASS |
|
|
Permit finaled
|