Inspections for the day of: Tuesday, November 10, 2015.
Number of inspections: 8
Percentage of inspections complete: 88 %
Percentage of inspections not complete: 13 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-01282 FIRE-Conference10/28/201511/4/2015 A 
follow up
BLD15-03223 FIRE-Final Inspection11/10/201511/10/201511/10/2015 3:20:48 PMPFAIL
Repair all exit signs and emergency lights, provide emergency lighting ina all paths of travel. Fire sprinkler coverage is missing in several rooms and possibly blocked in another with painted sprinkler heads. Sprinkler contractor to provide modifications. Install all ceiling tile. Provide verification that the fire alarm system is being monitored. Fire alarm system notification is missing in many areas and overspaced in others. Fire alarm contractor to provide modifications. Provide single action hardware for all exterior doors. Remove dead bolts from exterior doors. All access controlled egress doors to meet IFC 1008.1.9.8 or 1008.1.9.9. Provide fire extinguishers on mezzanines. The wall layout/mezzanines are not shown on the plans/does not match plans. Please verify with building plan reviewer.

I suggested to the contractor that a fire sprinkler contractor and a fire alarm contractor walk the building and provide code compliant systems.
BLD15-01983 FIRE-Final Inspection11/9/201511/10/201511/10/2015 3:14:25 PMPFAIL
provide smoke evac testing, provide "clouds" around the lower pendant sprinkler heads.
FIR15-00555 INSP-Sprinkler Rough-in11/10/201511/10/201511/10/2015 3:06:11 PMPPASS
underground supply line is ok for cover
FIR15-00573 INSP-Final Inspection11/9/201511/10/201511/10/2015 11:31:29 AMPPASS
permit finaled
FIR15-00382 INSP-Final Inspection11/5/201511/10/201511/10/2015 9:46:24 AMAFAIL
Provide Document Box, provide testing forms, provide map, provide correct batteries, provide knox box, plans show ion detectors but none are existing or installed. No actual testing was performed and plan mods may be needed.
BLD15-03430 FIRE-Final Inspection11/10/201511/10/201511/10/2015 8:34:00 AMPPASS
life safety passed
FIR15-00756 INSP-Final Inspection11/9/201511/10/201511/9/2015 1:43:50 PMAPASS
Permit finaled