Inspections for the day of: Wednesday, November 12, 1997.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE97-01916 INSP - Final11/12/199711/12/199711/13/1997 12:00:00 AMPPASS
11/12/97 336 - ok
ELE97-02453 INSP - Final11/12/199711/12/199711/13/1997 12:00:00 AMPPASS
11/12/97 336 - ok
ELE97-02912 INSP - Electrical Rough-In11/12/199711/12/199711/13/1997 12:00:00 AMPPASS
11/12/97 336 - 014 stairwells ok
ELE97-03454 INSP - Final11/12/199711/12/199711/13/1997 12:00:00 AMPFAIL
11/12/97 336 - disapproved Receps on kitchen circuit garage outlets not correct faceplate position
ELE97-03531 INSP - Electrical Rough-In11/12/199711/12/199711/13/1997 12:00:00 AMPPASS
11/12/97 336 - CEILING GRID ok
ELE97-03856 INSP - Ele Rough-In/Perm Svc11/12/199711/12/199711/13/1997 12:00:00 AMPFAIL
11/12/97 336 - REINSPECTION disapproved p/s damaged cable insulation
ELE97-03868 INSP - Permanent service11/12/199711/12/199711/12/1997 12:00:00 AM PASS
/ / 336 - ok
ELE97-02312 INSP - Framing/ Rough-in11/12/199711/12/199711/12/1997 12:00:00 AM PART
/ / 336 - Partial R/I 0k
ELE97-03880 INSP - Electrical Rough-In11/10/199711/12/199711/12/1997 12:00:00 AMAPASS
11/12/97 336 - ok
ELE97-03867 INSP - Electrical Rough-In11/10/199711/12/199711/12/1997 12:00:00 AMAPASS
11/12/97 336 - ok
ELE97-03868 INSP - Ele Rough-In/Perm Svc11/10/199711/12/199711/12/1997 12:00:00 AMAFAIL
11/12/97 336 - disapproved nail plates
ELE97-03460 INSP - Final11/10/199711/12/199711/12/1997 12:00:00 AMAPASS
11/12/97 336 - lock box 8147 is on gas meter ok
ELE97-03349 INSP - Final11/10/199711/12/199711/12/1997 12:00:00 AMAPASS
11/12/97 336 - lock box combo 8147 is on gas meter ok
ELE97-02312 INSP - Final11/10/199711/12/199711/12/1997 12:00:00 AMANR
11/12/97 336 - east end of ER not ready
ELE97-03842 INSP - Permanent service11/12/199711/12/199711/12/1997 12:00:00 AMPFAIL
11/12/97 336 - BEFORE 3:15 PLEASE CONTRACTOR WILL BE THERE disapproved Gr electrode flush connector on pvc main bonding jumper
ELE97-03866 INSP - Electrical Rough-In11/12/199711/12/199711/12/1997 12:00:00 AMPPASS
11/12/97 336 - VIDEO LAND/ WALLS ok
ELE97-03889 INSP - Ele Rough-In/Perm Svc11/12/199711/12/199711/12/1997 12:00:00 AMPFAIL
11/12/97 336 - THIS WILL BE PARTIAL R-IN FOR AREA IN ADDITION ONLY, AND ADDITION disapproved concrete encased electrode guy not opposed to drop grounds not made up
ELE97-03895 INSP - T/S and Final11/12/199711/12/199711/12/1997 12:00:00 AMPPASS
11/12/97 336 - ok
ELE97-03896 INSP - T/S and Final11/12/199711/12/199711/12/1997 12:00:00 AMPFAIL
11/12/97 336 - disapproved unused opening contamination coiver not remov
ELE97-03899 INSP - Permanent service11/12/199711/12/199711/12/1997 12:00:00 AMPPASS
11/12/97 336 - ok