Inspections for the day of: Friday, November 12, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00583 INSP-Final Inspection11/9/200411/12/200411/12/2004 12:00:00 AMANR
Jack; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner***CANCEL INSPECTION per permit desk - rescheduled for 11/15 11/12/2004 11:38:30 AM
FIR04-00519 INSP-Final Inspection11/9/200411/12/200411/12/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 11/9/2004 at 12:48:42 PM. Contact: ###-####. Single station alarm in room generate building alarm - not per matrix; speakers operated properly 11/12/2004 10:23:49 AM
FIR04-00607 INSP-Final Inspection11/9/200411/12/200411/12/2004 12:00:00 AMAPART
Hank; Phone #: ###-#### Internet Inspection Request from: Jan Rice This is a new Piranha Ansul system that includes the new water flow valve that is to remain locked for proper operation after the agent flows; the electrical/gas valve shut down on activation; install K-class extinguisher; the appliance were installed backwards from what was shown on plans - approved as nozzles are spaced per Ansul to provide complete coverage; will need air balance report 11/12/2004 10:30:47 AM
FIR04-00645 INSP-Alarm Testing11/10/200411/12/200411/12/2004 12:00:00 AMAPASS
Rick let me know what time works for you so that I can get it scheduled on my side. thanks Internet Inspection Request from: Rick Groom
FIR04-00519 INSP-Conference11/12/200411/12/200411/12/2004 12:00:00 AMAPART
Per Sam Rogers the detectors in the space will be a combo smoke/heat detector as this the type of system throughout the exsisting R occupancies; the smoke is local to the room and the heat generates general alarm; this info was passed on the Brian and Chris of Simplex 11/12/2004 10:56:25 AM
FIR04-00629 INSP-Final Inspection11/12/200411/12/200411/12/2004 12:00:00 AMPPASS
BLD04-01146 FIRE-Final Inspection11/12/200411/12/200411/12/2004 12:00:00 AMPPASS
All curtains were removed as the flame spread could not be verified; occupant load is 107 per Carl Westfall 11/12/2004 2:45:54 PM
FIR04-00468 INSP-Final Inspection11/12/200411/12/200411/12/2004 12:00:00 AMPPASS
BLD04-01253 FIRE-Final Inspection11/12/200411/12/200411/12/2004 12:00:00 AMPFAIL
Rated doors not latching; it appears card reader access control locks are being installed by tenant contractors - a separate permit will be required to interface with alarm system with motion sensor and push to exit button release; hang fire extinguishers 11/12/2004 2:50:26 PM
BLD04-01496 FIRE-Final Inspection11/12/200411/12/200411/12/2004 12:00:00 AMPPASS
Tom; Phone #: ###-#### Internet Inspection Request from: Jan Rice Sprinklers installed underneath walkway under the new terminal permit; fire alarms okay 11/12/2004 3:37:04 PM