Inspections for the day of: Friday, November 12, 2004.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00671 INSP-Final Inspection11/10/200411/12/200411/12/2004 12:00:00 AMAPASS
fire alarm finaled 11/12/2004 6:20:36 AM
BLD03-02060 FIRE-Final Inspection11/10/200411/12/200411/12/2004 12:00:00 AMAFAIL
Provide photo detector or push to silence feature at kitchen. Provide occupant load sign. Provide blank on exit door from laundry. Provide building address 11/12/2004 8:53:12 AM
BLD04-01043 FIRE-Final Inspection11/10/200411/12/200411/12/2004 12:00:00 AMAPASS
Fire life safety finaled 11/12/2004 7:52:29 AM
BLD04-02146 FIRE-Final Inspection11/10/200411/12/200411/12/2004 12:00:00 AMAPASS
fire life safety ok for door 11/12/2004 8:21:54 AM
FIR04-00393 INSP-Sprinkler Rough-in/Hydro11/10/200411/12/200411/12/2004 12:00:00 AMAPASS
Fire sprinkler finaled 11/12/2004 12:49:55 PM
FIR04-00686 INSP-Sprinkler Rough-in/Hydro11/10/200411/12/200411/12/2004 12:00:00 AMAFAIL
Provide letter stating hangers are ok on bottom truss or relocate hanger to top of truss per approved drawings. Test interconnection to fire alarm system. Above ground and underground hydro test passed. Flush and forward flush passed. 11/12/2004 12:51:46 PM
BLD04-01967 FIRE-Final Inspection11/11/200411/12/200411/12/2004 12:00:00 AMAPASS
fire life safety finaled 11/12/2004 6:21:23 AM
BLD04-00956 FIRE-Final Inspection11/11/200411/12/200411/12/2004 12:00:00 AMAPASS
fire life safety finaled 11/12/2004 9:46:25 AM
FIR04-00549 INSP-Final Inspection11/12/200411/12/200411/12/2004 12:00:00 AMAPASS
fire sprinkler finaled
FIR04-00573 INSP-Sprinkler Rough-in/Hydro11/12/200411/12/200411/12/2004 12:00:00 AMAPASS
conference room ok to cover 11/12/2004 8:54:38 AM
BLD04-01994 FIRE-Final Inspection11/12/200411/12/200411/12/2004 12:00:00 AMPPASS
Fire life safety finaled 11/12/2004 1:21:22 PM
FIR04-00479 INSP-Alarm Testing11/12/200411/12/200411/12/2004 12:00:00 AMPFAIL
Provide map at facp. Duct detectors are mounted incorrectly. Retest them when done. Provide responding address for fire dept at the monitoring station. Provide nfpa 72 forms 11/12/2004 1:01:21 PM
FIR04-00693 INSP-Final Inspection11/12/200411/12/200411/12/2004 12:00:00 AMPFAIL
duct smoke detectors are located incorrectly. Provide signage on facp room door per review note 14. Provide map per note 6. Provide breaker lock on breaker. 11/12/2004 4:00:39 PM