FIR04-00671
| INSP-Final Inspection | 11/10/2004 | 11/12/2004 | 11/12/2004 12:00:00 AM | A | PASS |
|
|
fire alarm finaled 11/12/2004 6:20:36 AM
|
BLD03-02060
| FIRE-Final Inspection | 11/10/2004 | 11/12/2004 | 11/12/2004 12:00:00 AM | A | FAIL |
|
|
Provide photo detector or push to silence feature at kitchen. Provide occupant load sign. Provide blank on exit door from laundry. Provide building address 11/12/2004 8:53:12 AM
|
BLD04-01043
| FIRE-Final Inspection | 11/10/2004 | 11/12/2004 | 11/12/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 11/12/2004 7:52:29 AM
|
BLD04-02146
| FIRE-Final Inspection | 11/10/2004 | 11/12/2004 | 11/12/2004 12:00:00 AM | A | PASS |
|
|
fire life safety ok for door 11/12/2004 8:21:54 AM
|
FIR04-00393
| INSP-Sprinkler Rough-in/Hydro | 11/10/2004 | 11/12/2004 | 11/12/2004 12:00:00 AM | A | PASS |
|
|
Fire sprinkler finaled 11/12/2004 12:49:55 PM
|
FIR04-00686
| INSP-Sprinkler Rough-in/Hydro | 11/10/2004 | 11/12/2004 | 11/12/2004 12:00:00 AM | A | FAIL |
|
|
Provide letter stating hangers are ok on bottom truss or relocate hanger to top of truss per approved drawings. Test interconnection to fire alarm system. Above ground and underground hydro test passed. Flush and forward flush passed. 11/12/2004 12:51:46 PM
|
BLD04-01967
| FIRE-Final Inspection | 11/11/2004 | 11/12/2004 | 11/12/2004 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 11/12/2004 6:21:23 AM
|
BLD04-00956
| FIRE-Final Inspection | 11/11/2004 | 11/12/2004 | 11/12/2004 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 11/12/2004 9:46:25 AM
|
FIR04-00549
| INSP-Final Inspection | 11/12/2004 | 11/12/2004 | 11/12/2004 12:00:00 AM | A | PASS |
|
|
fire sprinkler finaled
|
FIR04-00573
| INSP-Sprinkler Rough-in/Hydro | 11/12/2004 | 11/12/2004 | 11/12/2004 12:00:00 AM | A | PASS |
|
|
conference room ok to cover 11/12/2004 8:54:38 AM
|
BLD04-01994
| FIRE-Final Inspection | 11/12/2004 | 11/12/2004 | 11/12/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 11/12/2004 1:21:22 PM
|
FIR04-00479
| INSP-Alarm Testing | 11/12/2004 | 11/12/2004 | 11/12/2004 12:00:00 AM | P | FAIL |
|
|
Provide map at facp. Duct detectors are mounted incorrectly. Retest them when done. Provide responding address for fire dept at the monitoring station. Provide nfpa 72 forms 11/12/2004 1:01:21 PM
|
FIR04-00693
| INSP-Final Inspection | 11/12/2004 | 11/12/2004 | 11/12/2004 12:00:00 AM | P | FAIL |
|
|
duct smoke detectors are located incorrectly. Provide signage on facp room door per review note 14. Provide map per note 6. Provide breaker lock on breaker. 11/12/2004 4:00:39 PM
|