BLD09-00965
| FIRE-Final Inspection | 11/12/2009 | 11/12/2009 | 11/12/2009 3:34:24 PM | P | PASS |
|
|
Life safety passed.
|
FIR09-00484
| INSP-Sprinkler Rough-in/Hydro | 11/10/2009 | 11/12/2009 | 11/12/2009 2:33:56 PM | A | PASS |
|
|
All of the sprinkler piping can be covered except in the show room area.
|
BLD09-01856
| FIRE-Conference | 11/10/2009 | 11/12/2009 | 11/12/2009 2:19:30 PM | A | DONE |
|
|
I went over the life safety requirements for this project with the general contractor.
|
BLD09-01982
| FIRE-Final Inspection | 11/12/2009 | 11/12/2009 | 11/12/2009 11:31:18 AM | A | FAIL |
|
|
The damper for the smoke evac system failed to operate when the smoke detector was activated. The other items have been corrected.
|
BLD09-01479
| FIRE-Final Inspection | 11/10/2009 | 11/12/2009 | 11/12/2009 11:29:53 AM | A | FAIL |
|
|
One exit sign/emergency light did not function and the thumbturn lock needs removed at the main exit as discussed
|
FIR09-00422
| INSP-Final Inspection | 11/11/2009 | 11/12/2009 | 11/12/2009 10:01:32 AM | A | PASS |
|
|
Permit finaled. Deficiencies corrected.
|