ELE15-01812
| Electrical Rough-In | 11/11/2015 | 11/12/2015 | 11/12/2015 3:47:01 PM | P | PASS |
|
|
Inspection for the site pole base. Phone #: ###-#### Inspection requested via web by William Salts 2 west pole bases rough in ok cover
|
ELE15-02489
| Electrical Rough-In | 11/12/2015 | 11/12/2015 | 11/12/2015 3:13:41 PM | P | PASS |
|
|
Please inspect the ceiling for cover. Phone #: ###-#### Inspection requested via web by Spencer McLean Area 2.3 grid rough in ok cover
|
ELE15-03677
| Final | 11/12/2015 | 11/12/2015 | 11/12/2015 3:08:41 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Randy Fletcher Permanent service inspection required. Spoke with contractor on this permit he did not install service pedistal on lot. Asked him to find out who did and call me so I can verify responcible party. 550.10(I)- A metal or rigid non-metallic conduit from disconnecting means to underside of mobile home shall be installed 250.24- Grounding electrode system required. Unable to verify existing.
|
ELE15-03515
| Final | 11/11/2015 | 11/12/2015 | 11/12/2015 2:05:51 PM | P | PASS |
|
|
We are requesting a final inspection for tomorrow 11/12/15 in the afternoon. Our contact is Trent Hammon @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate Final ok
|
ELE15-03457
| Final | 11/11/2015 | 11/12/2015 | 11/12/2015 1:42:53 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman 110.12- As you enter 3 receptacle outlets on wall to right not working. 314.25- All boxes shall have covers.
|
ELE15-03056
| Final | 11/12/2015 | 11/12/2015 | 11/12/2015 1:05:35 PM | A | FAIL |
|
|
All work is complete. Low voltage boxes, for speakers, are incomplete, owner to finish. Side door is open for access into shop. Phone #: ###-#### Inspection requested via web by Kurt Carlson 406.12(A)- All areas specified in 210.52, all 120volt 15 and 20 amp receptacle outlets shall be listed tamper resistant receptacles.
|
ELE15-03672
| Final | 11/11/2015 | 11/12/2015 | 11/12/2015 12:43:26 PM | A | PASS |
|
|
new pylon sign Phone #: ###-#### Inspection requested via web by Mark Morgan Circuit to sign underground final ok
|
ELE15-03672
| Electrical Rough-In | 11/12/2015 | 11/12/2015 | 11/12/2015 12:42:49 PM | P | PASS |
|
|
new pylon sign Phone #: ###-#### Inspection requested via web by Mark Morgan Underground to sign rough in ok cover
|
ELE15-03657
| Rough-In Permanent Service | 11/10/2015 | 11/12/2015 | 11/12/2015 12:14:40 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey Rough in ok cover p/s o/h n ok
|
ELE15-03669
| Electrical Rough-In | 11/11/2015 | 11/12/2015 | 11/12/2015 11:43:49 AM | A | PASS |
|
|
If you have any questions, please call Jake ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan South back addition of master bed, bath, closet, laundry areas rough in ok cover
|
ELE15-02696
| Final | 11/11/2015 | 11/12/2015 | 11/12/2015 11:21:58 AM | A | FAIL |
|
|
Bob Thomas Phone #: ###-#### Inspection requested via web by Kerri Hamilton 110.7- Wiring integrity- 2 receptacle outlets not working. Post outlet and north hall. Several luminaires not working, some flash. 210.8(B)- Receptacle outlets located within 6' of sink shall have GFCI protection.
|
ELE15-03671
| Electrical Rough-In | 11/11/2015 | 11/12/2015 | 11/12/2015 10:46:33 AM | A | PASS |
|
|
Gate next to garage is open , yellow city permit on gate Phone #: ###-#### Inspection requested via web by Jesse Fuentes Sunroom in rear central of back. Rough in ok cover
|
ELE15-02787
| Final | 11/10/2015 | 11/12/2015 | 11/12/2015 10:32:18 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov No access to garage. Key did not work on garage.
|
ELE15-02831
| Final | 11/10/2015 | 11/12/2015 | 11/12/2015 10:27:58 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 210.52(C)(3)- If peninsula counter space is 24" or more from its connecting edge a receptacle outlet shall be located at end.
|
ELE15-03654
| Rough-In Permanent Service | 11/10/2015 | 11/12/2015 | 11/12/2015 9:49:17 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Told if foam seal again before inspection job will fail until all is removed. Rough in ok cover p/s u/g n ok
|
ELE15-03221
| Final | 11/12/2015 | 11/12/2015 | 11/12/2015 9:32:31 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn No access to garage walls due to trash build up. Remove and recall.
|
ELE15-03086
| Final | 11/12/2015 | 11/12/2015 | 11/12/2015 8:57:25 AM | A | PASS |
|
|
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ELE15-03203
| Final | 11/12/2015 | 11/12/2015 | 11/12/2015 8:44:00 AM | A | PASS |
|
|
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ELE15-03590
| Rough-In Permanent Service | 11/10/2015 | 11/12/2015 | 11/12/2015 8:01:36 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Duplicate request.
|
ELE15-03590
| Final | 11/10/2015 | 11/12/2015 | 11/12/2015 7:52:03 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Needed rough in permanent service
|
ELE13-00910
| ELE-Aging Inspection | 11/12/2015 | 11/12/2015 | 11/12/2015 7:51:01 AM | | CANC |
|
|
|
ELE13-00903
| ELE-Aging Inspection | 11/12/2015 | 11/12/2015 | 11/12/2015 7:49:52 AM | | CANC |
|
|
|
ELE13-00855
| ELE-Aging Inspection | 11/12/2015 | 11/12/2015 | 11/12/2015 7:49:22 AM | | CANC |
|
|
|
ELE13-00908
| ELE-Aging Inspection | 11/12/2015 | 11/12/2015 | 11/12/2015 7:49:08 AM | | CANC |
|
|
|
ELE15-03515
| Final | 11/6/2015 | 11/12/2015 | 11/11/2015 3:53:23 PM | A | CANC |
|
|
We are requesting a final inspection for Thursday 11/12/15 in the AM. Our contact for this is Trent @ ###-####. Thank you Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
|
ELE15-03396
| Electrical Rough-In | 11/10/2015 | 11/12/2015 | 11/10/2015 10:11:25 AM | A | CANC |
|
|
We need an underground inspection for Thursday. Thank you! Phone #: ###-#### >> Inspection requested via web by Stacie Tasker Inspection cancelled from web by: Stacie Tasker
|