Inspections for the day of: Wednesday, November 13, 2002.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-01055 FIRE-Final Inspection11/11/200211/13/200211/13/2002 12:00:00 AMAPASS
life safety finaled 11/13/2002 1:17:50 PM
FIR02-00381 INSP-Sprinkler Rough-in/Hydro11/12/200211/13/200211/13/2002 12:00:00 AMPPASS
24 hour air test for the dry system is ok. It lost just over a pound of pressure 11/13/2002 1:17:21 PM
FIR02-00183 INSP-Final Inspection11/7/200211/13/200211/13/2002 12:00:00 AMPPASS
brad ###-####
FIR02-00287 INSP-Final Inspection11/7/200211/13/200211/13/2002 12:00:00 AMPFAIL
provide tamper switch on the gate valve on fire pump test line, verify weather proof pull station assembly, provide hi/low pressure switch for anechoic chamber dry pipe valve 11/14/2002 1:41:05 PM
FIR02-00286 INSP-Final Inspection11/7/200211/13/200211/13/2002 12:00:00 AMPFAIL
provide tamper switch on gate valve on fire pump test line, verify weather proof pull station assembly, provide hi/low pressure switch for anechoic chamber dry pipe valve 11/14/2002 1:42:18 PM