ELE06-03179
| ELE-Aging Inspection | 11/13/2006 | 11/13/2006 | 11/15/2006 7:41:37 AM | | CANC |
|
|
|
ELE06-04206
| Final | 11/13/2006 | 11/13/2006 | 11/13/2006 4:07:48 PM | P | NR |
|
|
please call when you are going out so i can get you inside to see water bond and furnace.###-#### clay. thank you! Internet Inspection Request from: Bob Glenn called
|
ELE06-04208
| Electrical Rough-In | 11/13/2006 | 11/13/2006 | 11/13/2006 4:07:25 PM | P | PASS |
|
|
roger; Phone #: ###-#### Internet Inspection Request from: Cathy ok
|
ELE06-03352
| Rough-In Permanent Service | 11/13/2006 | 11/13/2006 | 11/13/2006 4:07:04 PM | P | PASS |
|
|
all 4 units ok p/s u/g new ok
|
ELE06-03046
| Final | 11/13/2006 | 11/13/2006 | 11/13/2006 3:28:28 PM | P | FAIL |
|
|
jamie Note: ufier; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. fee due called 210.52(C) needs required outlets 12" 2ft 4ft rule peninsular counter has backsplash, same spacing for countertop in din rm, note outlet covered by wallpaper S wall M bed rmcheck your work also install all shelves in closets 410.8
|
ELE06-02599
| Final | 11/13/2006 | 11/13/2006 | 11/13/2006 2:21:45 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Rohl corr called left message, 210.52(C) needs required outlets din rm counter, 210.8 bad gfci counter right of refer, note need intructions for heater in M bath and also jtub
|
ELE06-00671
| Final | 11/13/2006 | 11/13/2006 | 11/13/2006 1:44:05 PM | P | PASS |
|
|
tye ###-#### ok card signed
|
ELE06-03352
| Rough-In Permanent Service | 11/10/2006 | 11/13/2006 | 11/13/2006 11:47:56 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson see pm request
|
ELE06-04127
| Rough-In Permanent Service | 11/13/2006 | 11/13/2006 | 11/13/2006 11:45:21 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 11/13/2006 at 6:47:52 AM. Contact: ###-####. corr. all corr. not made nail plates called left message
|
ELE06-02587
| Final | 11/10/2006 | 11/13/2006 | 11/13/2006 11:43:03 AM | A | FAIL |
|
|
Customer is available in am with 15 minutes notice to unlock home. Please call her (Phyllis) at ###-####. Thank you!; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney corr. box fill and not ready
|
ELE06-03777
| Final | 11/9/2006 | 11/13/2006 | 11/13/2006 11:40:21 AM | A | CANC |
|
|
This is for a final above the grid ceiling.; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa see added r/i
|
ELE06-03777
| Electrical Rough-In | 11/13/2006 | 11/13/2006 | 11/13/2006 11:40:04 AM | A | PART |
|
|
This is for a final above the grid ceiling.; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa no final grid ok
|
ELE06-04116
| Electrical Rough-In | 11/9/2006 | 11/13/2006 | 11/13/2006 10:29:25 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 11/9/2006 at 2:52:58 PM. Contact: ###-####. Note: please call 1/2 hr prior r/i 5 rms for hvac units anop
|
ELE06-03078
| Final | 11/9/2006 | 11/13/2006 | 11/13/2006 9:31:18 AM | A | FAIL |
|
|
FINAL INSPECTIONPLEASE CALL AJ WITH INSPECTION QUESTIONS AND/OR RESULTS; Phone #: ###-#### Internet Inspection Request from: todd hall corr called left message 314.16 box fill island counter recept, 250.148 grd all metal boxes island, 300.14 short grd wires island counter, corrections for owner 110.26 shall remove cabinets in garage for panel clearence, 410.8 needs clearence for fixture MB closet new shelf above fixture
|
ELE06-04202
| Temporary Service | 11/9/2006 | 11/13/2006 | 11/13/2006 8:51:02 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Shane Vigil t/s u/g new ok
|
ELE06-02818
| Electrical Rough-In | 11/10/2006 | 11/13/2006 | 11/13/2006 8:23:13 AM | A | PART |
|
|
Need Undeground Insp morning please!!! Pouring on Monday.; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok
|