ELE05-00058
| Final | 11/8/2006 | 11/13/2006 | 11/14/2006 11:47:29 AM | A | NH |
|
|
bob; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left messages, will have to recall to set up inspection
|
ELE06-03456
| Electrical Rough-In | 11/13/2006 | 11/13/2006 | 11/13/2006 4:44:02 PM | P | PASS |
|
|
chuck; Phone #: ###-#### Internet Inspection Request from: Darla Downs ric ok
|
ELE06-04126
| Electrical Rough-In | 11/13/2006 | 11/13/2006 | 11/13/2006 4:27:44 PM | P | PART |
|
|
this is a partial inspection, any questions please call Jesse Collingsworth; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok to cover exterior office walls only
|
ELE06-04205
| Electrical Rough-In | 11/11/2006 | 11/13/2006 | 11/13/2006 4:14:52 PM | A | FAIL |
|
|
Internet Inspection Request from: Phil Baker called, left corr notice, nec 300.4 300.4(A)&(D) edge of holes and nm cable sjall be 1 1/4" from edge of framing member, 314.20 box shall be flush with finished surface, BCC all u/g shall be inspected before cover, need to verify free length of conductor for outside recpt
|
ELE06-04139
| Temporary Service | 11/13/2006 | 11/13/2006 | 11/13/2006 1:47:02 PM | P | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/s o/h n ok
|
ELE06-02762
| Electrical Rough-In | 11/13/2006 | 11/13/2006 | 11/13/2006 1:30:03 PM | P | PART |
|
|
jim; Phone #: ###-#### Note: please call will like to meet with you Internet Inspection Request from: Cathy Chiles ok to cover, need to see make-up before devices installed, garage area only
|
ELE06-02658
| Final | 11/13/2006 | 11/13/2006 | 11/13/2006 12:51:26 PM | P | PASS |
|
|
don; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
|
ELE06-03537
| Permanent Service | 11/13/2006 | 11/13/2006 | 11/13/2006 12:41:23 PM | P | PASS |
|
|
john ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g rec ok
|
ELE06-03451
| Conference | 11/9/2006 | 11/13/2006 | 11/13/2006 12:19:53 PM | A | DONE |
|
|
Scheduled by a contractor via Hello! on 11/9/2006 at 4:11:22 PM. Contact: ###-####. agreed for subpanel, but told owner needs to run load calcs and probably requires 200A service, talked about afcis and general elect
|
ELE06-04196
| Electrical Rough-In | 11/9/2006 | 11/13/2006 | 11/13/2006 11:58:27 AM | A | PASS |
|
|
Internet Inspection Request from: Cathy Chiles ric ok
|
ELE06-03720
| Final | 11/9/2006 | 11/13/2006 | 11/13/2006 11:24:09 AM | A | PASS |
|
|
jackie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called and told to put in panel schedule, ok to final
|
ELE06-04065
| Final | 11/7/2006 | 11/13/2006 | 11/13/2006 10:45:41 AM | A | FAIL |
|
|
FINAL ON SERVICE UPGRADE. ; Phone #: ###-#### Internet Inspection Request from: Barry Kendall called, left message, corr notice, nec 250.50 shall use warter pipe as gnd electrode where enters bldg, 110.26(A) work space shall be clear and safe in front of elect service, 230.24(A) service conductor over roof shall be 8', range and dryer shall be 4-wire ckts
|
ELE06-04194
| Conference | 11/9/2006 | 11/13/2006 | 11/13/2006 10:07:19 AM | A | DONE |
|
|
sean - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith talked about panel change, ok to cover except where panel will be
|
ELE05-02003
| Final | 11/10/2006 | 11/13/2006 | 11/13/2006 9:42:56 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 11/10/2006 at 1:55:24 PM. Contact: ###-####. west 4th floor rooms anop ok to final
|
ELE06-03275
| Electrical Rough-In | 11/13/2006 | 11/13/2006 | 11/13/2006 9:13:48 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 11/13/2006 at 6:54:34 AM. Contact: ###-####.rear ceiling only ok to cover
|
ELE06-00113
| Electrical Rough-In | 11/9/2006 | 11/13/2006 | 11/13/2006 8:37:47 AM | A | PART |
|
|
greg Note: heat trace and pool eq room; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles light boxes as noted on plan ok
|
ELE06-00113
| Electrical Rough-In | 11/9/2006 | 11/13/2006 | 11/13/2006 8:37:01 AM | A | FAIL |
|
|
greg Note: ceiling ins 4th floor; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles grid damaged, wires not fastened
|
ELE06-00113
| Final | 11/9/2006 | 11/13/2006 | 11/13/2006 8:36:14 AM | A | PASS |
|
|
greg Note: part final 5th floor; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final anop part, rooms only
|
ELE06-02364
| Permanent Service | 11/13/2006 | 11/13/2006 | 11/13/2006 12:00:00 AM | P | CANC |
|
|
###-#### - wayne; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|