Inspections for the day of: Tuesday, November 13, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00450 FIR-Aging Inspection11/13/200711/13/200711/14/2007 10:05:04 AM DEFR
wip
BLD06-03088 FIRE-Final Inspection11/13/200711/13/200711/14/2007 9:26:10 AMPNR
Brian; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
FIR07-00360 INSP-Final Inspection11/9/200711/13/200711/13/2007 3:34:16 PMPPASS
Test flow and tamper switches to alrm panel test smoke detector and pull station. Call monitoring company and verifie signals and address. Test complete.
FIR07-00448 INSP-Final Inspection11/13/200711/13/200711/13/2007 3:31:29 PMPPASS
Connection to fire alarm was complete.
BLD07-01488 FIRE-Final Inspection11/12/200711/13/200711/13/2007 3:29:19 PMPFAIL
approved plan notes were not on site, they were not ready for life safety.
BLD07-01097 FIRE-Final Inspection11/12/200711/13/200711/13/2007 3:27:08 PMPFAIL
One exit light in building did not function see plans for location. Egress lights on outside of building did not function see plan for details.Duct smokes were not ready to be tested. Fence was not put up but was shown on plans,It shows to gates that are means of egress, fence and gates need to be put up before a fire life safety, or submit with out fence and gates.
FIR07-00205 INSP-Final Inspection11/12/200711/13/200711/13/2007 10:57:31 AMPCANC
Mike B is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus
FIR06-00940 INSP-Final Inspection11/12/200711/13/200711/13/2007 10:56:53 AMPCANC
Mike B is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus
FIR06-00844 INSP-Final Inspection11/12/200711/13/200711/13/2007 10:56:24 AMPCANC
Mike B is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus
FIR07-00905 INSP-Final Inspection11/9/200711/13/200711/13/2007 10:55:18 AMAPART
Under ground piping is ok to cover.
BLD07-02475 FIRE-Final Inspection11/9/200711/13/200711/13/2007 10:35:43 AMAPASS
All repairs were made as per Forrest notes.
BLD07-01422 FIRE-Final Inspection11/13/200711/13/200711/13/2007 9:55:00 AMAPASS
All exit signs and and exit lights are battery backup plus they are tied into the emergency generator.One exit sign pointed wrong direction changed while finishing inspection.
FIR07-00706 INSP-Final Inspection11/12/200711/13/200711/13/2007 9:18:55 AMAPASS
This permit was for the fire alarm testing
FIR07-00706 INSP-Alarm Testing11/13/200711/13/200711/13/2007 9:01:05 AMPPART
complete test of fire alarm panel duct smokes,flow and tamper switches and interconnnetion to clean agent fike panel.KR