Inspections for the day of: Thursday, November 13, 2008.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00712 INSP-Final Inspection11/12/200811/13/200811/14/2008 8:25:51 AMPFAIL
The voice evac sytem had bad static and humming in the speakers. The static was not allowing the voice to come thru clearly. KR
BLD08-02174 FIRE-Final Inspection11/13/200811/13/200811/13/2008 3:36:22 PMPFAIL
Repair the existing exit lights and emergency lighting. All other items are ok.
FIR08-00743 INSP-Final Inspection11/11/200811/13/200811/13/2008 3:34:25 PMPPASS
Permit finaled
FIR07-01031 INSP-Sprinkler Rough-in11/12/200811/13/200811/13/2008 11:41:18 AMAPART
See the city approved plans for locations where sprinkler piping can be covered. I noted flat face bushing being used on the second floor and showed the fitter the code section that prohibits their use. Also the second floor piping as installed does not match the approved drawings.