FIR08-00712
| INSP-Final Inspection | 11/12/2008 | 11/13/2008 | 11/14/2008 8:25:51 AM | P | FAIL |
|
|
The voice evac sytem had bad static and humming in the speakers. The static was not allowing the voice to come thru clearly. KR
|
BLD08-02174
| FIRE-Final Inspection | 11/13/2008 | 11/13/2008 | 11/13/2008 3:36:22 PM | P | FAIL |
|
|
Repair the existing exit lights and emergency lighting. All other items are ok.
|
FIR08-00743
| INSP-Final Inspection | 11/11/2008 | 11/13/2008 | 11/13/2008 3:34:25 PM | P | PASS |
|
|
Permit finaled
|
FIR07-01031
| INSP-Sprinkler Rough-in | 11/12/2008 | 11/13/2008 | 11/13/2008 11:41:18 AM | A | PART |
|
|
See the city approved plans for locations where sprinkler piping can be covered. I noted flat face bushing being used on the second floor and showed the fitter the code section that prohibits their use. Also the second floor piping as installed does not match the approved drawings.
|