Inspections for the day of: Thursday, November 13, 2014.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00474 INSP-Sprinkler Rough-in/Hydro11/13/201411/13/201411/13/2014 3:43:43 PMPPASS
See the city approved plans for additional rooms where piping can be covered.
FIR14-00696 INSP-Final Inspection11/12/201411/13/201411/13/2014 3:38:33 PMPPASS
permit finaled
FIR14-00458 INSP-Final Inspection11/12/201411/13/201411/13/2014 3:38:09 PMPFAIL
Install 7amp hour batteries or provide verification 4.5 are adequate
FIR14-00676 INSP-Final Inspection11/12/201411/13/201411/13/2014 3:35:55 PMPPASS
Permit finaled
FIR14-00691 INSP-Final Inspection11/12/201411/13/201411/13/2014 11:22:31 AMPCANC
Cancel per John Phone #: ###-####
FIR14-00689 INSP-Final Inspection11/12/201411/13/201411/13/2014 11:21:27 AMPCANC
Cancel per John Phone #: ###-####
FIR14-00584 INSP-Final Inspection11/12/201411/13/201411/13/2014 11:19:44 AMPCANC
Cancel per discussion and rescheduled for tomorrow
BLD14-02598 FIRE-Final Inspection11/13/201411/13/201411/13/2014 10:32:09 AMPPASS
Life safety passed
FIR14-00798 INSP-Final Inspection11/13/201411/13/201411/13/2014 10:31:52 AMPPASS
Permit finaled
BLD14-02370 FIRE-Final Inspection11/13/201411/13/201411/13/2014 10:31:27 AMPPASS
Life safety passed. Duct smoke detector relocated to return ducting
BLD14-00452 FIRE-Final Inspection11/13/201411/13/201411/13/2014 8:56:51 AMAFAIL
Inspection turned into a conference for life safety items. There are no approved plans or small documents on site so no full inspection was performed. I noted that one manual pull station for a kitchen hood suppression system does not meet distance code so fire dept approval will be needed, one exit discharge light was non-functional. But door hardware appears adequate as well as fire extinguishers.
BLD14-01294 FIRE-Final Inspection11/12/201411/13/201411/13/2014 8:52:33 AMAFAIL
Provide sticker at the main exit as per review note #2, provide ADA hardware for the restroom door as per review note #6 and provide address numbers as discussed.
BLD14-01293 FIRE-Final Inspection11/12/201411/13/201411/13/2014 8:51:38 AMAFAIL
Provide sticker at main exit as per review note #2, provide ADA hardware on the Restroom door as per review note #6 and provide address numbers as discussed.
BLD14-01014 FIRE-Final Inspection11/12/201411/13/201411/13/2014 8:50:26 AMACANC
No fire life safety sign off required.
FIR14-00704 INSP-Final Inspection11/11/201411/13/201411/12/2014 9:09:38 AMACANC
As early as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brianderson Inspection cancelled via mobile web on Wednesday, November 12, 2014.