Inspections for the day of: Friday, November 13, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03670 Electrical Rough-In11/13/201511/13/201511/13/2015 1:58:22 PMPPASS
Inspection for Idaho Power to restore power. Phone #: ###-#### Inspection requested via web by Randy Fletcher p/s o/h rec ok
ELE15-03641 Permanent Service11/12/201511/13/201511/13/2015 12:55:57 PMPPASS
would like call ahead; Mitch Phone #: ###-#### p/s o/h rec ok
ELE15-02355 Final11/13/201511/13/201511/13/2015 12:25:58 PMPFAIL
Phone #: ###-#### Inspection requested via web by John VanZandt 210.8(5)unfinished basements all 120V receptacles shall haveGFCI protection 210.12(a) bedrooms in a dwelling shall have AFCI protection(master bed has GFCI) 422.31 permanently installed appliances shall have means of lock out(dishwasher not set) 406.6 faceplates required (kitchen)
ELE15-03683 Rough-In Permanent Service11/12/201511/13/201511/13/2015 11:10:52 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn rough-in ok cover p/s u/g n ok
ELE15-02280 Final11/11/201511/13/201511/13/2015 10:31:56 AMAPASS
Phone #: ###-#### Inspection requested via web by Kendra Lanham bathroom and laundry final ok
ELE15-03690 Electrical Rough-In11/12/201511/13/201511/13/2015 9:43:54 AMAPASS
Phone #: ###-#### Inspection requested via web by Terry Scott upstairs back beds and bath ok cover
ELE15-03391 Final11/13/201511/13/201511/13/2015 9:32:28 AMAFAIL
Phone #: ###-#### Inspection requested via web by John Edwards 210.8 receptacles in a kitchen shall be GFCI reading open ground aswell
ELE15-03175 Final11/12/201511/13/201511/13/2015 9:18:11 AMAPASS
Garage code 7606 Phone #: ###-#### Inspection requested via web by Charles Davis correction fixed final ok
ELE15-02563 Final11/12/201511/13/201511/13/2015 9:02:31 AMAPASS
Lock Box is located on front hose bib. Code is mjs Phone #: ###-#### Inspection requested via web by Eric Schroeder back bed and master bed final ok
ELE15-03687 Temporary Service11/12/201511/13/201511/13/2015 9:02:27 AMAPASS
Inspection requested via web by Brandon Hillman talked with contractor about changing out pole to a 4x4 p/s u/g n ok
ELE15-03687 Final11/12/201511/13/201511/12/2015 6:01:58 PMACANC
Phone #: ###-#### >> Inspection requested via web by Brandon Hillman Inspection cancelled from web by: Brandon Hillman