Inspections for the day of: Tuesday, November 13, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-04353 Final11/13/201811/13/201811/13/2018 3:14:03 PMPNR
sorry to reschedule, point of contact changed. Please call Jake for Access to suite 302 at ###-####. Thank You, Steve Phone #: ###-#### Inspection requested via web by Steve Blackmer See r/i inspection
ELE18-04353 Electrical Rough-In11/13/201811/13/201811/13/2018 3:13:24 PMPNR
sorry to reschedule, point of contact changed. Please call Jake for Access to suite 302 at ###-####. Thank You, Steve Phone #: ###-#### Inspection requested via web by Steve Blackmer
Contact informed not ready, called 2nd contact to check and call in when ready.
ELE18-04322 Electrical Rough-In11/13/201811/13/201811/13/2018 2:32:03 PMPPASS
Rough-in Inspection for Level 1 bathrooms
Contact Jon Novak
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Level 1 bathroom ceilings and receptacles rough in ok cover
ELE18-02032 Final11/12/201811/13/201811/13/2018 2:02:08 PMAFAIL
Please call 30 minutes before on site to give contact time to show up for inspector. Phone #: ###-#### Inspection requested via web by Jim Noll
426.28- Ground fault protection for equipment shall be in place for final.
ELE18-02748 Final11/12/201811/13/201811/13/2018 1:07:58 PMANH
Phone #: ###-#### Inspection requested via web by Hidajet Zahic
Unit locked, no one on site. Called and left message to recall when accessible.
ELE18-04189 Conference11/12/201811/13/201811/13/2018 12:53:48 PMADONE
Please contact Dean Gernaat to schedule a time to meet. ###-####. Phone #: ###-#### Inspection requested via web by Dean Gernaat
Discussed options for a conduit or flat conductor cable to floor receptacle location required by 210.71. Due to structural issues unable to route conduit unless allowed to have less than 2" concrete cover.
As per Daryl DeGrange ok to install in concrete floor of office to floor receptacle.
ELE18-04353 Electrical Rough-In11/12/201811/13/201811/13/2018 8:36:23 AMACANC
Please call Jim for access at ###-#### Thank You Phone #: ###-#### >> Inspection requested via web by Steve Blackmer Inspection cancelled from web by: Steve Blackmer
ELE18-04353 Final11/12/201811/13/201811/13/2018 8:36:19 AMACANC
Please call Jim for access at ###-#### Thank You Phone #: ###-#### >> Inspection requested via web by Steve Blackmer Inspection cancelled from web by: Steve Blackmer