All 2ND Floor storage, comm rm , hallway and units 201,202,203,204,205,206,207,208,209,210,211,212,213,214,215,216,217,218,219.,Stairwell#1 and Stairwell#2,1st Floor Lobby,Bathrm, Trash rm,Bike rm,Sprinkler riser rm, mail rm, Move in rm and roof top condenser units Phone #: 573- 1573 Inspection requested via web by Tom Betty All corrections listed are for roof top mini split systems. 330.6- All connectors used on coated MC cable shall be listed and identified for use. 725.3(J)- Bushings shall be provided and properly installed for all wiring marked class 2R. 725.124- Class 2 power sources shall be clearly marked. Measured 208 volts on terminal with class 2 wiring connected. As per Daryl DeGrange wiring marked class 3 ok due to documentation found on Southwire web site deffinition and explanation.
|