Inspections for the day of: Tuesday, November 13, 2018.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02862 Final11/12/201811/13/201811/13/2018 12:56:12 PMAFAIL
All 2ND Floor storage, comm rm , hallway and units 201,202,203,204,205,206,207,208,209,210,211,212,213,214,215,216,217,218,219.,Stairwell#1 and Stairwell#2,1st Floor Lobby,Bathrm, Trash rm,Bike rm,Sprinkler riser rm, mail rm, Move in rm and roof top condenser units Phone #: 573-
1573 Inspection requested via web by Tom Betty All corrections listed are for roof top mini split systems.
330.6- All connectors used on coated MC cable shall be listed and identified for use.
725.3(J)- Bushings shall be provided and properly installed for all wiring marked class 2R.
725.124- Class 2 power sources shall be clearly marked. Measured 208 volts on terminal with class 2 wiring connected.
As per Daryl DeGrange wiring marked class 3 ok due to documentation found on Southwire web site deffinition and explanation.
ELE18-03802 Electrical Rough-In11/12/201811/13/201811/13/2018 12:01:28 PMAPASS
Randy. Phone #: ###-#### Inspection requested via web by Sean DeLacy rough-in ok cover half walls
ELE18-03537 Electrical Rough-In11/12/201811/13/201811/13/2018 12:00:56 PMAPASS
Ceiling inspection request Phone #: ###-#### Inspection requested via web by Jim Noll rough-in ceiling grid ok cover