ELE02-03527
| Temporary Service | 11/13/2002 | 11/14/2002 | 11/14/2002 12:00:00 AM | A | PART |
|
|
###-#### u/g for future t/s ok 11/14/2002 11:02:28 AM
|
ELE02-02360
| Final | 11/13/2002 | 11/14/2002 | 11/14/2002 12:00:00 AM | A | PASS |
|
|
###-#### ok 11/14/2002 12:33:03 PM
|
ELE01-03021
| Final | 11/14/2002 | 11/14/2002 | 11/14/2002 12:00:00 AM | P | FAIL |
|
|
###-#### russell job not ready partial correction posted 110.3(B) install grd bushings on all conduits entering non metallic boxes manufactrues instructionssupport all raceways and secure within 3 ft of boxes 314.25,250.110,406.5 grd all covers u/g jboxes 11/14/2002 6:18:01 PM
|
ELE02-03548
| Rough-In Permanent Service | 11/14/2002 | 11/14/2002 | 11/14/2002 12:00:00 AM | P | FAIL |
|
|
###-#### KEVIN cor. posted met with contractor 210.52 (A&B) outlet for wall spce over 6ft NE upstairs bedrm, and remove light fixture from small appliance circuit in din. rm replace 2 gang boxes with broken clamps 314.20 outside boxes shall be flush with siding, 250.6and 200.7 shall not use 2 wire romex for 3and 4 ways 11/14/2002 3:44:23 PM
|
ELE02-03550
| Final | 11/14/2002 | 11/14/2002 | 11/14/2002 12:00:00 AM | P | PASS |
|
|
###-#### ok 11/14/2002 4:29:06 PM
|
ELE02-01383
| Final | 11/13/2002 | 11/14/2002 | 11/14/2002 12:00:00 AM | P | PASS |
|
|
bruce ###-#### ok 11/14/2002 2:41:14 PM
|