Inspections for the day of: Friday, November 14, 2003.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRuss Owen
TitleBLD-COM/RES INSPECTOR
Phone #794-9473
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-00706 BLD-Energy code compliance11/13/200311/14/200311/14/2003 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 11/13/2003 at 3:56:02 PM. Contact: ###-####. this schell and core showed R-30 ceiling , but has foam of R-18 also 2x4 walls shown on plans with R-19 on com check , architect re-ran report but the west space can not have R-19 value in a 2x4 wall will only get R-15 need to bump up another area or calc some of ceilng at penthoses to R-30 contractor on site will address and recall. 11/13/2003 11:53:16 PM Also 3 rear doors added which architect has ok"d. but need details for landings.11/13/2003 11:53:47 PM 11/13/2003 11:55:05 PM
BLD03-01928 BLD-Framing/Rough-in11/13/200311/14/200311/14/2003 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 11/13/2003 at 3:58:51 PM. Contact: ###-####. needs to install per manufacture or free floating system 11/13/2003 11:44:18 PM 11/13/2003 11:44:57 PM
BLD03-02157 BLD-Framing/Rough-in11/13/200311/14/200311/14/2003 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 11/13/2003 at 4:01:39 PM. Contact: ###-####. need to install per manufaturer or free floating system. 11/13/2003 11:44:52 PM
BLD03-01854 BLD-Final11/10/200311/14/200311/14/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 11/10/2003 at 5:00:47 PM. Contact: ###-####. Ok for temp pending fire for perm. 11/13/2003 6:37:16 PM
BLD03-00363 BLD-Foundation11/13/200311/14/200311/14/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 11/13/2003 at 12:12:48 PM. Contact: ###-####. Wip. 11/13/2003 7:04:45 PM
BLD03-01468 BLD-Framing/Rough-in11/13/200311/14/200311/14/2003 12:00:00 AMAPART
Gene --- check the straps.; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes. 11/13/2003 7:04:14 PM
BLD03-01739 BLD-Final11/13/200311/14/200311/14/2003 12:00:00 AMPFAIL
Mark; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Went to job 2 times once at 11:00 and as requested 3:00 still needs fire life safety. 11/13/2003 11:46:40 PM
BLD03-02661 BLD-Footing11/14/200311/14/200311/14/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 11/14/2003 at 6:38:56 AM. Contact: ###-####.
BLD03-02024 BLD-Framing/Rough-in11/14/200311/14/200311/14/2003 12:00:00 AMPFAIL
Kole; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Complete prior c/n all items posted 2 nd c/n for 2 items. 11/13/2003 8:23:37 PM
BLD03-00913 BLD-Final11/14/200311/14/200311/14/2003 12:00:00 AMPFAIL
Kole; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Note need one c/n item completed ladder out of basement. 11/13/2003 9:48:30 PM
BLD03-02467 BLD-Framing/Rough-in11/14/200311/14/200311/14/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 11/14/2003 at 10:20:20 AM. Contact: ###-####. Interior walls ok but exterior exit door has swing wrong on wrong will resolve before final. 11/13/2003 11:54:46 PM
BLD03-02076 BLD-Framing/Rough-in11/14/200311/14/200311/14/2003 12:00:00 AMPCANC
Dan --- please call first...late afternoon.; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
BLD02-02583 BLD-Final11/14/200311/14/200311/14/2003 12:00:00 AMPPASS
Buck; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Ok perm oc letters from engineer and specilal inspector on file. 11/13/2003 10:27:36 PM
BLD03-01964 BLD-Energy code compliance11/14/200311/14/200311/14/2003 12:00:00 AMPPASS
Dwane; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
BLD03-02076 BLD-Final11/13/200311/14/200311/14/2003 12:00:00 AMPPART
ok temp oc needs doors hung and grab bar extended also paper dispencers relocated. 11/13/2003 11:48:09 PM