Inspections for the day of: Friday, November 14, 2003.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00448 INSP-Sprinkler Rough-in/Hydro11/13/200311/14/200311/14/2003 12:00:00 AMADONE
Inspection was actually a conference on sprinklers spaced off of obstructions in the nfpa 13 areas 11/14/2003 11:10:20 AM
FIR03-00670 INSP-Sprinkler Rough-in/Hydro11/13/200311/14/200311/14/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 11/13/2003 at 10:45:44 AM. Contact: ###-####.
BLD03-00319 FIRE-Sprinkler Rough-in11/13/200311/14/200311/14/2003 12:00:00 AMAPASS
###-####- rod Fire life safety finaled 11/14/2003 10:34:00 AM
BLD03-00442 FIRE-Final Inspection11/13/200311/14/200311/14/2003 12:00:00 AMAPASS
Life safety finaled 11/14/2003 9:58:41 AM
FIR03-00657 INSP-Sprinkler Rough-in/Hydro11/13/200311/14/200311/14/2003 12:00:00 AMAPASS
Underground supply piping is now ok to cover 11/14/2003 9:20:13 AM
FIR03-00600 INSP-Sprinkler Rough-in/Hydro11/14/200311/14/200311/14/2003 12:00:00 AMPPART
Underground supply line hydro test is OK. Above ground hydro test failed 11/14/2003 12:51:29 PM
FIR03-00342 INSP-Final Inspection11/14/200311/14/200311/14/2003 12:00:00 AMPCANC
per the contractor the project is not ready 11/14/2003 4:19:33 PM
FIR03-00550 INSP-Final Inspection11/14/200311/14/200311/14/2003 12:00:00 AMPFAIL
verify all signals, test phone lines, repair duct smoke detector, provide remote alarm led for duct detector in corridor 11/14/2003 3:30:13 PM
FIR03-00555 INSP-Sprinkler Rough-in/Hydro11/14/200311/14/200311/14/2003 12:00:00 AMPPASS
Underground hydro is OK
BLD03-02076 FIRE-Final Inspection11/13/200311/14/200311/14/2003 12:00:00 AMPPASS
fire life safety finaled. Structural inspector to verify door hardware when installed 11/14/2003 3:23:32 PM
BLD03-01739 FIRE-Final Inspection11/13/200311/14/200311/14/2003 12:00:00 AMPFAIL
Mark; Phone #: ###-#### Fire alarm failed. Fire life safety will be ok to sign off when fire alarm is complete 11/14/2003 3:41:36 PM
FIR03-00532 INSP-Final Inspection11/10/200311/14/200311/14/2003 12:00:00 AMPFAIL
Duct smoke detectors in blockbuster video need to be retested since the wrong address came in at the monitoring service. All other items are ok. 11/14/2003 2:07:11 PM