Inspections for the day of: Monday, November 14, 2005.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01286 ELE-Aging Inspection11/14/200511/14/200511/15/2005 3:26:06 PM PASS
ELE05-01675 ELE-Aging Inspection11/14/200511/14/200511/15/2005 3:13:10 PM PEND
called they will follow up and request inspection
ELE05-04109 Temporary Service11/14/200511/14/200511/14/2005 5:01:39 PMPPASS
darrell ###-#### t/s o/h new ok
ELE05-04113 Rough-In Permanent Service11/14/200511/14/200511/14/2005 5:01:14 PMPPASS
ron ###-#### r/i ok p/s new ok
ELE05-04006 Final11/14/200511/14/200511/14/2005 4:19:26 PMPPASS
If possible, call after 3:00pm and I can meet at location...thanks.; Phone #: ###-#### Internet Inspection Request from: Vince Bourner ok hot tub
ELE05-04118 Electrical Rough-In11/14/200511/14/200511/14/2005 3:35:38 PMPPART
rick ###-#### -call 1st before insp u/g from new store to carwash
ELE05-04111 Temporary Service11/14/200511/14/200511/14/2005 2:34:34 PMPPASS
darrell ###-#### t/s o/h new ok
ELE05-04057 Final11/14/200511/14/200511/14/2005 2:13:10 PMPNR
After 1 pm; Phone #: ###-#### Internet Inspection Request from: Dana Moyer called contractor needs to grd 250.52(A)(1), or bond 250.104(A)(1) water system
ELE05-03012 Final11/14/200511/14/200511/14/2005 1:33:46 PMPFAIL
###-#### dennis cor called 410.8 clearence MB closet fixture, no power to 1/2 the outlets upstair N & W walls
ELE05-04054 Electrical Rough-In11/14/200511/14/200511/14/2005 12:18:56 PMPPART
Phone #: ###-#### Internet Inspection Request from: Heather Packer kit r/i ok
ELE05-03484 Final11/10/200511/14/200511/14/2005 11:57:51 AMAPASS
###-####--gayle--call 1st before insp for homeowner ok card signed
ELE05-01612 ELE-Aging Inspection11/14/200511/14/200511/14/2005 10:23:10 AM DONE
ELE05-04047 Rough-In Permanent Service11/10/200511/14/200511/14/2005 10:00:46 AMAPASS
Scheduled by a contractor via Hello! on 11/10/2005 at 1:54:41 PM. Contact: ###-####. r/i ok p/s u/g new ok
ELE05-04024 Electrical Rough-In11/11/200511/14/200511/14/2005 9:38:07 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney cor. called 300.4 nail plates and 11/4", 330.30 no tape allowed to secure MC cable, and secure within 12" of boxes
ELE04-00911 Permanent Service11/10/200511/14/200511/14/2005 8:49:16 AMAFAIL
will; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. fee due posted called 312.5 conn for GEC, 250.24(A)(5) isolate grds and neutrals at subpanel
ELE05-01848 Rough-In Permanent Service11/11/200511/14/200511/14/2005 8:11:49 AMAPASS
Corrections have been made. Contact Harvey Reyna.; Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA p/s o/h new ok
ELE05-01612 DOC - Permit Finaled11/14/200511/14/200511/14/2005 12:00:00 AMAPASS
was done by bill
ELE05-04057 Rough-In Permanent Service11/14/200511/14/200511/14/2005 12:00:00 AMPPASS
After 1 pm; Phone #: ###-#### Internet Inspection Request from: Dana Moyer r/i ok p/s o/h rec. ok
ELE05-03341 Final11/14/200511/14/200511/14/2005 12:00:00 AMPPASS
ok owner secured contractor to wire hot tub