Inspections for the day of: Monday, November 14, 2005.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04121 Rough-In Permanent Service11/14/200511/14/200511/14/2005 4:55:38 PMPCANC
chris ###-#### inspection came in as another address, talked to contr and office both. Will need to do in am with proper address
ELE05-04112 Rough-In Permanent Service11/14/200511/14/200511/14/2005 4:53:45 PMPFAIL
brian ###-#### called contr, left corr notice, 300.4(A)&(D) 1 1/4" shall be maintained for bored holes and nm cable shall be from edge of framing member, 800.133(A)(1) comm cable shall not be run with class 1 wiring,110.12(A) there shall be no open wiring holes in boxes, 314.20 boxes shall be flush with combustibloe material (out back recpt), BCC job id sticker shall be posted
ELE05-02341 Final11/14/200511/14/200511/14/2005 4:48:23 PMPPASS
earl call 1/2 before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--pending bld fn met owner, told to provide gfci in garage, w/p recpt covers outside and flex to range hood. ok to final
ELE05-04098 Electrical Rough-In11/10/200511/14/200511/14/2005 4:43:40 PMPCANC
tony ###-#### see conf
ELE05-03276 Electrical Rough-In11/14/200511/14/200511/14/2005 4:41:51 PMPPASS
stu; Phone #: ###-#### Internet Inspection Request from: Barbara Moore told elect to strap emt a couple places, ric front soffit only ok
ELE05-04036 Temporary Service11/14/200511/14/200511/14/2005 4:39:20 PMPFAIL
Scheduled by a contractor via Hello! on 11/14/2005 at 10:20:24 AM. Contact: ###-####. called contr, left message, left corr notice, 110.12(C) there shall be no broken parts(50 A rcpt)
ELE05-03661 Electrical Rough-In11/14/200511/14/200511/14/2005 3:50:42 PMPPART
Scheduled by a contractor via Hello! on 11/14/2005 at 8:09:32 AM. Contact: ###-####. so 1/2 clg ok to cover
ELE05-04064 Temporary Service11/14/200511/14/200511/14/2005 2:17:03 PMPPASS
michael; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa t/s u/g n ok
ELE05-03088 Final11/14/200511/14/200511/14/2005 1:59:32 PMPPASS
Please final Edwards Theatre signs Internet Inspection Request from: Radon Elaina ok to final
ELE05-03852 Final11/14/200511/14/200511/14/2005 1:44:52 PMPPASS
Scheduled by a contractor via Hello! on 11/14/2005 at 8:08:39 AM. signed card, ok to fnali
ELE05-03871 Final11/14/200511/14/200511/14/2005 1:41:50 PMPPASS
josh; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to final
ELE05-04117 Electrical Rough-In11/14/200511/14/200511/14/2005 10:53:32 AMPPASS
brian ###-#### walls only ok to cover
ELE05-03522 Final11/14/200511/14/200511/14/2005 10:52:50 AMPPASS
Scheduled by a contractor via Hello! on 11/14/2005 at 7:38:18 AM. Contact: ###-####. signed occ card, ok to final
ELE05-04077 Temporary Service11/10/200511/14/200511/14/2005 10:51:33 AMAPASS
paul; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/s u/g n ok
ELE05-03620 Rough-In Permanent Service11/10/200511/14/200511/14/2005 10:07:56 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called contr, left corr notice,334.30 nm cable shall be stapled wthin 12" of box,314.17(C) nm shall be stapled within 8" of box,300.4(A)&(D) bored holes and cable shall be 1 1/4" from edge of framing member,800.133(A) comm cable shall not be run with power wiring, 312.5 abrasion protection shall be provided for conductors entering enclosures.
ELE05-02783 Permanent Service11/10/200511/14/200511/14/2005 9:32:01 AMAFAIL
richard ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles told owner, left corr notice,250.24(B) bonding jumper shall be installed from gnded conductor to equip gnd
ELE05-04100 Rough-In Permanent Service11/11/200511/14/200511/14/2005 8:47:16 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ric ok p/s u/g n ok
ELE05-03533 Electrical Rough-In11/10/200511/14/200511/14/2005 8:30:08 AMAPART
request ealy as possible//mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to pour 7 pole bases
ELE05-04096 Rough-In Permanent Service11/10/200511/14/200511/14/2005 8:24:20 AMAPASS
ron ###-#### ric ok p/s u/g n ok
ELE05-04098 Conference11/14/200511/14/200511/14/2005 12:00:00 AMPDONE
tony ###-#### too many items to write, so made conf, not ri