ELE06-04218
| Permanent Service | 11/14/2006 | 11/14/2006 | 11/15/2006 1:09:18 PM | P | FAIL |
|
|
bill; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called told contr he needs to check out kitchen shack wiring, and wire it then call for r/i inspection permit was for a R V comm. kit. shack
|
ELE06-04226
| Electrical Rough-In | 11/14/2006 | 11/14/2006 | 11/15/2006 8:48:29 AM | P | PASS |
|
|
Work performed by Tony Norton.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz
|
ELE06-02694
| Final | 11/14/2006 | 11/14/2006 | 11/14/2006 4:46:42 PM | P | NH |
|
|
scott, please call 1st for access; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called left message for access no response had to leave the area
|
ELE06-04227
| Electrical Rough-In | 11/14/2006 | 11/14/2006 | 11/14/2006 4:40:59 PM | P | NH |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles notice posted called house is boarded up
|
ELE06-03668
| Electrical Rough-In | 11/13/2006 | 11/14/2006 | 11/14/2006 4:21:07 PM | P | PART |
|
|
Jerod Note: underground; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles power and phone ok
|
ELE06-03978
| Electrical Rough-In | 11/14/2006 | 11/14/2006 | 11/14/2006 4:01:23 PM | P | PART |
|
|
UFER Ground inspection; Phone #: ###-#### Internet Inspection Request from: Alan Lusk ok for concrete
|
ELE06-02308
| Final | 11/14/2006 | 11/14/2006 | 11/14/2006 3:38:51 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy corr. called 210.63 needs outside gfci recept fwithin 25ft of a/c unit
|
ELE06-03298
| Electrical Rough-In | 11/14/2006 | 11/14/2006 | 11/14/2006 2:30:01 PM | P | PART |
|
|
eric - bonding for spa ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith bond for spa set into ground ok still needs E grid ?
|
ELE05-03962
| Rough-In Permanent Service | 11/14/2006 | 11/14/2006 | 11/14/2006 2:13:37 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen see added conf.
|
ELE05-03962
| Conference | 11/14/2006 | 11/14/2006 | 11/14/2006 2:13:14 PM | P | DONE |
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen conference ok only
|
ELE06-03352
| Electrical Rough-In | 11/13/2006 | 11/14/2006 | 11/14/2006 11:57:47 AM | A | PASS |
|
|
ali ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok r/i p/s u/g new ok
|
ELE06-04218
| Final | 11/13/2006 | 11/14/2006 | 11/14/2006 10:09:04 AM | A | FAIL |
|
|
william ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr. called no final p/s 250.64(E) shall use kisted fiiting for GEC, 250.56 needs 2 grd rods, 250.24(A)(1) shall make connection between grd and neutral
|
ELE06-04127
| Rough-In Permanent Service | 11/14/2006 | 11/14/2006 | 11/14/2006 10:06:32 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/14/2006 at 7:22:42 AM. Contact: ###-####. r/i ok p/s u/g new ok
|
ELE06-04206
| Permanent Service | 11/14/2006 | 11/14/2006 | 11/14/2006 9:13:42 AM | A | FAIL |
|
|
PLEASE CALL WHEN YOU ARE DONE. THANK YOU .CLAY-###-#### Internet Inspection Request from: Bob Glenn called needs plastic conn. for GEC needs #4 to u/g water system. seal KOs and install covers on elect furnace
|
ELE06-03796
| Final | 11/13/2006 | 11/14/2006 | 11/14/2006 8:30:47 AM | A | CANC |
|
|
mike -call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called wrong address correct address is on lemp also p/s not final
|
ELE06-03542
| Rough-In Permanent Service | 11/13/2006 | 11/14/2006 | 11/14/2006 8:13:42 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange r/i p/s o/h new ok
|