ELE07-03814
| Electrical Rough-In | 11/14/2007 | 11/14/2007 | 11/14/2007 4:38:26 PM | P | PASS |
|
|
john - uffer ground Phone #: ###-#### ok to cover concrete encased electrode
|
ELE07-02082
| Electrical Rough-In | 11/13/2007 | 11/14/2007 | 11/14/2007 3:45:21 PM | P | FAIL |
|
|
Steve Phone #: ###-#### BCC all make-up shall be done, no devices installed, NEC 250.86 shall provide and wire ground wire in metal boxes, 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing members, 300.14 at 6" free conductor shall be provided before tails installed
|
ELE07-01088
| Electrical Rough-In | 11/14/2007 | 11/14/2007 | 11/14/2007 2:46:24 PM | P | PART |
|
|
shaun Phone #: ###-#### walls only anop ok to cover
|
ELE07-03787
| Permanent Service | 11/14/2007 | 11/14/2007 | 11/14/2007 1:47:33 PM | P | FAIL |
|
|
call for access mike volgamore insurance specialty services Phone #: ###-#### Internet Inspection Request from: joe wheeler called contractor, left correction notice, BCC no violations shall be retained, NEC 110.26 shall provide spaces about electrical equipment
|
ELE07-03503
| Electrical Rough-In | 11/13/2007 | 11/14/2007 | 11/14/2007 1:07:21 PM | P | PASS |
|
|
DUSTIN NOTE: PLEASE CALL 1/2 HR TO MEET WITH Phone #: ###-#### ric ok
|
ELE07-03774
| Rough-In Permanent Service | 11/14/2007 | 11/14/2007 | 11/14/2007 12:39:05 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson see ri and p/s
|
ELE07-03774
| Permanent Service | 11/14/2007 | 11/14/2007 | 11/14/2007 12:38:47 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called contractor, left correction notice, nec 110.26 shall provide working clearances about electrical equipment, BCC shall post address, shall provide approved set of plans on job, shall post job id sticker, told contractor he must provide above to get next inspection
|
ELE07-03774
| Electrical Rough-In | 11/14/2007 | 11/14/2007 | 11/14/2007 12:30:07 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ric ok
|
ELE07-03130
| Electrical Rough-In | 11/13/2007 | 11/14/2007 | 11/14/2007 10:39:33 AM | A | FAIL |
|
|
casey Phone #: ###-#### called owner, left correction notice, nec 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing members (both sides), 300.4(F) shall provide insulating bushing for ser cable at sub-panel, 250.86 sahll provide and wire ground screw in metal box
|
ELE07-02524
| Final | 11/13/2007 | 11/14/2007 | 11/14/2007 9:49:40 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/13/2007 at 2:40:26 PM. Contact: ###-####. ok to final, signed structural card
|
ELE07-03450
| Final | 11/13/2007 | 11/14/2007 | 11/14/2007 9:14:58 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Alison Pennington ok to final, signed occupancy card
|
ELE07-03707
| Electrical Rough-In | 11/13/2007 | 11/14/2007 | 11/14/2007 8:50:01 AM | A | PASS |
|
|
Stu; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt wall only ok to cover
|
ELE07-02834
| Electrical Rough-In | 11/13/2007 | 11/14/2007 | 11/14/2007 8:28:58 AM | A | PASS |
|
|
jared - please call 1/2 hr prior for access Phone #: ###-#### ok to cover upstairs and patio ceiling only
|