Inspections for the day of: Wednesday, November 14, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03814 Electrical Rough-In11/14/200711/14/200711/14/2007 4:38:26 PMPPASS
john - uffer ground Phone #: ###-#### ok to cover concrete encased electrode
ELE07-02082 Electrical Rough-In11/13/200711/14/200711/14/2007 3:45:21 PMPFAIL
Steve Phone #: ###-#### BCC all make-up shall be done, no devices installed, NEC 250.86 shall provide and wire ground wire in metal boxes, 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing members, 300.14 at 6" free conductor shall be provided before tails installed
ELE07-01088 Electrical Rough-In11/14/200711/14/200711/14/2007 2:46:24 PMPPART
shaun Phone #: ###-#### walls only anop ok to cover
ELE07-03787 Permanent Service11/14/200711/14/200711/14/2007 1:47:33 PMPFAIL
call for access mike volgamore insurance specialty services Phone #: ###-#### Internet Inspection Request from: joe wheeler called contractor, left correction notice, BCC no violations shall be retained, NEC 110.26 shall provide spaces about electrical equipment
ELE07-03503 Electrical Rough-In11/13/200711/14/200711/14/2007 1:07:21 PMPPASS
DUSTIN NOTE: PLEASE CALL 1/2 HR TO MEET WITH Phone #: ###-#### ric ok
ELE07-03774 Rough-In Permanent Service11/14/200711/14/200711/14/2007 12:39:05 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson see ri and p/s
ELE07-03774 Permanent Service11/14/200711/14/200711/14/2007 12:38:47 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called contractor, left correction notice, nec 110.26 shall provide working clearances about electrical equipment, BCC shall post address, shall provide approved set of plans on job, shall post job id sticker, told contractor he must provide above to get next inspection
ELE07-03774 Electrical Rough-In11/14/200711/14/200711/14/2007 12:30:07 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ric ok
ELE07-03130 Electrical Rough-In11/13/200711/14/200711/14/2007 10:39:33 AMAFAIL
casey Phone #: ###-#### called owner, left correction notice, nec 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing members (both sides), 300.4(F) shall provide insulating bushing for ser cable at sub-panel, 250.86 sahll provide and wire ground screw in metal box
ELE07-02524 Final11/13/200711/14/200711/14/2007 9:49:40 AMAPASS
Scheduled by a contractor via Hello! on 11/13/2007 at 2:40:26 PM. Contact: ###-####. ok to final, signed structural card
ELE07-03450 Final11/13/200711/14/200711/14/2007 9:14:58 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Alison Pennington ok to final, signed occupancy card
ELE07-03707 Electrical Rough-In11/13/200711/14/200711/14/2007 8:50:01 AMAPASS
Stu; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt wall only ok to cover
ELE07-02834 Electrical Rough-In11/13/200711/14/200711/14/2007 8:28:58 AMAPASS
jared - please call 1/2 hr prior for access Phone #: ###-#### ok to cover upstairs and patio ceiling only