Inspections for the day of: Wednesday, November 14, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00802 INSP-Sprinkler Rough-in11/14/200711/14/200711/15/2007 2:15:50 PMPPART
Install is okay for cover at the drop ceilings, noted one existing head at the reception area in need of removal.
BLD07-02607 FIRE-Conference11/14/200711/14/200711/15/2007 8:14:06 AMPNH
Scheduled by a contractor via Hello! on 11/14/2007 at 8:52:15 AM. Contact: ###-####. Called contact three times and left one message, no one available.
FIR07-00807 INSP-Final Inspection11/9/200711/14/200711/15/2007 8:05:41 AMPPART
Per K. Roule phase one portion of the fire alarm work is satisfactory.
FIR07-00858 INSP-Final Inspection11/14/200711/14/200711/15/2007 8:03:56 AMPPASS
Fire alarm testing passed per site inspection completed by K. Roule, permit finaled.
FIR06-00940 INSP-Final Inspection11/13/200711/14/200711/15/2007 8:02:42 AMAFAIL
Due to improperly spaced and blocked heads at several locations.
FIR07-00205 INSP-Final Inspection11/13/200711/14/200711/15/2007 8:01:11 AMAFAIL
Noted several locations where heads are overspaced, blocked, or installed beyond listed spacing and max. allowable area.
FIR07-00589 INSP-Final Inspection11/13/200711/14/200711/15/2007 7:58:04 AMAPASS
Fire alarm work passed inspection, permit finaled.
BLD06-00470 FIRE-Final Inspection11/14/200711/14/200711/14/2007 2:44:13 PMPFAIL
Need to tag the provided PFE, manual surface bolts are not permitted, provide signage at the door to the FACP/Riser room.
BLD07-00954 FIRE-Final Inspection11/13/200711/14/200711/14/2007 2:01:24 PMANR
Need project related fire sprinkler and hood suppression system permits finaled prior to request for a life safety inspection.
BLD07-01097 FIRE-Final Inspection11/13/200711/14/200711/14/2007 1:49:44 PMAFAIL
Not all corrections have been made per K. Roule.
BLD07-01488 FIRE-Final Inspection11/13/200711/14/200711/14/2007 1:47:54 PMAPASS
Life safety inspection passed per K. Roule.
FIR07-00840 INSP-Conference11/14/200711/14/200711/14/2007 11:25:58 AMPNR
Conference to discuss schedule for permit final.
FIR07-00568 INSP-Final Inspection11/14/200711/14/200711/14/2007 11:19:18 AMAPASS
Fire sprinkler demo permit finaled.
FIR06-00844 INSP-Final Inspection11/13/200711/14/200711/14/2007 11:16:39 AMAPASS
UG fire supply line permit finaled.
FIR07-00877 INSP-Sprinkler Rough-in11/13/200711/14/200711/14/2007 11:13:27 AMAPART
Need to add hangers for arm-overs at some locations due to static pressures exceeding 100psi., remiander of OH mods are acceptable per site visit by K. Roule.
BLD06-02449 FIRE-Final Inspection11/13/200711/14/200711/14/2007 11:10:14 AMAPASS
Shell/Demo permit passed inspection.
FIR07-00451 FIR-Aging Inspection11/14/200711/14/200711/14/2007 9:30:37 AM DEFR
Under construction.
BLD07-02477 FIRE-Final Inspection11/13/200711/14/200711/14/2007 12:00:00 AMPCANC
MARK Phone #: ###-####