FIR07-00802
| INSP-Sprinkler Rough-in | 11/14/2007 | 11/14/2007 | 11/15/2007 2:15:50 PM | P | PART |
|
|
Install is okay for cover at the drop ceilings, noted one existing head at the reception area in need of removal.
|
BLD07-02607
| FIRE-Conference | 11/14/2007 | 11/14/2007 | 11/15/2007 8:14:06 AM | P | NH |
|
|
Scheduled by a contractor via Hello! on 11/14/2007 at 8:52:15 AM. Contact: ###-####. Called contact three times and left one message, no one available.
|
FIR07-00807
| INSP-Final Inspection | 11/9/2007 | 11/14/2007 | 11/15/2007 8:05:41 AM | P | PART |
|
|
Per K. Roule phase one portion of the fire alarm work is satisfactory.
|
FIR07-00858
| INSP-Final Inspection | 11/14/2007 | 11/14/2007 | 11/15/2007 8:03:56 AM | P | PASS |
|
|
Fire alarm testing passed per site inspection completed by K. Roule, permit finaled.
|
FIR06-00940
| INSP-Final Inspection | 11/13/2007 | 11/14/2007 | 11/15/2007 8:02:42 AM | A | FAIL |
|
|
Due to improperly spaced and blocked heads at several locations.
|
FIR07-00205
| INSP-Final Inspection | 11/13/2007 | 11/14/2007 | 11/15/2007 8:01:11 AM | A | FAIL |
|
|
Noted several locations where heads are overspaced, blocked, or installed beyond listed spacing and max. allowable area.
|
FIR07-00589
| INSP-Final Inspection | 11/13/2007 | 11/14/2007 | 11/15/2007 7:58:04 AM | A | PASS |
|
|
Fire alarm work passed inspection, permit finaled.
|
BLD06-00470
| FIRE-Final Inspection | 11/14/2007 | 11/14/2007 | 11/14/2007 2:44:13 PM | P | FAIL |
|
|
Need to tag the provided PFE, manual surface bolts are not permitted, provide signage at the door to the FACP/Riser room.
|
BLD07-00954
| FIRE-Final Inspection | 11/13/2007 | 11/14/2007 | 11/14/2007 2:01:24 PM | A | NR |
|
|
Need project related fire sprinkler and hood suppression system permits finaled prior to request for a life safety inspection.
|
BLD07-01097
| FIRE-Final Inspection | 11/13/2007 | 11/14/2007 | 11/14/2007 1:49:44 PM | A | FAIL |
|
|
Not all corrections have been made per K. Roule.
|
BLD07-01488
| FIRE-Final Inspection | 11/13/2007 | 11/14/2007 | 11/14/2007 1:47:54 PM | A | PASS |
|
|
Life safety inspection passed per K. Roule.
|
FIR07-00840
| INSP-Conference | 11/14/2007 | 11/14/2007 | 11/14/2007 11:25:58 AM | P | NR |
|
|
Conference to discuss schedule for permit final.
|
FIR07-00568
| INSP-Final Inspection | 11/14/2007 | 11/14/2007 | 11/14/2007 11:19:18 AM | A | PASS |
|
|
Fire sprinkler demo permit finaled.
|
FIR06-00844
| INSP-Final Inspection | 11/13/2007 | 11/14/2007 | 11/14/2007 11:16:39 AM | A | PASS |
|
|
UG fire supply line permit finaled.
|
FIR07-00877
| INSP-Sprinkler Rough-in | 11/13/2007 | 11/14/2007 | 11/14/2007 11:13:27 AM | A | PART |
|
|
Need to add hangers for arm-overs at some locations due to static pressures exceeding 100psi., remiander of OH mods are acceptable per site visit by K. Roule.
|
BLD06-02449
| FIRE-Final Inspection | 11/13/2007 | 11/14/2007 | 11/14/2007 11:10:14 AM | A | PASS |
|
|
Shell/Demo permit passed inspection.
|
FIR07-00451
| FIR-Aging Inspection | 11/14/2007 | 11/14/2007 | 11/14/2007 9:30:37 AM | | DEFR |
|
|
Under construction.
|
BLD07-02477
| FIRE-Final Inspection | 11/13/2007 | 11/14/2007 | 11/14/2007 12:00:00 AM | P | CANC |
|
|
MARK Phone #: ###-####
|