Inspections for the day of: Friday, November 14, 2008.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-03025 Rough-In Permanent Service11/14/200811/14/200811/14/2008 2:47:36 PMPPASS
CONTACT JACK Phone #: ###-#### Internet Inspection Request from: Emmet Bushman r/i p/s u/g new ok
ESC08-00865 General Inspection11/14/200811/14/200811/14/2008 2:45:15 PMPFAIL
called left # message, needs bmps inplace and clean sidewalks, street , and gutter
ELE08-01975 Final11/14/200811/14/200811/14/2008 2:16:02 PMPNR
Phone #: ###-#### Internet Inspection Request from: Terrie Dickson called still needs equip grd bus installed
ELE08-01449 Final11/13/200811/14/200811/14/2008 2:15:21 PMAPART
Partial Final - Bedroom Units Only - see TRoy if any questions ###-#### Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe north and east wings ok
ELE08-02281 Final11/13/200811/14/200811/14/2008 1:13:16 PMPCANC
###-#### Internet Inspection Request from: Lynn Cable ok
ELE08-02511 ELE-Aging Inspection11/14/200811/14/200811/14/2008 12:17:22 PM CANC
ELE08-02511 Final11/14/200811/14/200811/14/2008 12:17:12 PMPPASS
should of been finaled at time of p/s inspection
ELE07-04134 DOC - Permit Expired11/14/200811/14/200811/14/2008 12:16:01 PMPPASS
ELE08-01787 Final11/13/200811/14/200811/14/2008 10:30:13 AMAPASS
Kyle Phone #: ###-#### ok card signed
ESC08-00959 General Inspection11/14/200811/14/200811/14/2008 10:10:29 AMAPASS
ok told RP needs to post yellow card , he did
ELE08-03026 Electrical Rough-In11/13/200811/14/200811/14/2008 10:08:50 AMAPART
Floor Box ###-#### Internet Inspection Request from: Todd Holbrook ok
ELE08-02286 Electrical Rough-In11/13/200811/14/200811/14/2008 9:43:28 AMAFAIL
Thomas Phone #: ###-#### corr 314.43 nails not allowed in plastic boxes, 334.23 protect all cables within 6ft of attic access, 110.3(B) remove gas range 120v recept from micro wave circuit, shall have p/s ready
ELE08-02248 Electrical Rough-In11/13/200811/14/200811/14/2008 8:51:13 AMAFAIL
Brian Phone #: ###-#### met contr needs GEC from p/s to concrete encased electrode, staple cables within 8" of plastic boxes, 12" of subpanel
ELE08-02281 Final11/12/200811/14/200811/13/2008 5:52:38 PMACANC
homeowner should be home for access, thanks Phone #: ###-#### Internet Inspection Request from: Lynn Cable Inspection cancelled from web by: Lynn Cable
ELE08-03032 Temporary Service11/13/200811/14/200811/13/2008 3:31:17 PMAPASS
temporary power pole Phone #: ###-#### Internet Inspection Request from: Stephen Kren t/s u/g new ok