Inspections for the day of: Friday, November 14, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-02264 FIRE-Final Inspection11/14/200811/14/200811/17/2008 6:29:44 PMPPASS
Fire life safety passed field inspection.
FIR08-00654 INSP-Sprinkler Rough-in11/14/200811/14/200811/14/2008 5:03:52 PMPPART
One overspaced head relocated while on site, remainder of overhead modifications are approved for cover.
BLD08-00567 FIRE-Final Inspection11/13/200811/14/200811/14/2008 5:01:44 PMPPASS
Life safety inspection passed.
FIR08-00730 INSP-Final Inspection11/14/200811/14/200811/14/2008 5:01:12 PMPFAIL
Testing postponed until smoke detectors throughout are relocated.
FIR08-00595 INSP-Sprinkler Rough-in11/13/200811/14/200811/14/2008 1:29:50 PMAPART
Reinspection for adjusted upright head locations in the truss webs at the roof deck passed. Noted three non-sprinklered concealed spaces at the SW round- locations marked on plans- in need of coverage or meet exceptions per NFPA.
FIR08-00613 INSP-Final Inspection11/13/200811/14/200811/14/2008 1:26:02 PMAPART
Fire alarm testing completed for a portion of the tenant remodel finished to date as marked on approved plan set. Need as-built plans for accurate device locations and addresses- also provide updated map at the main FACP.
BLD08-01101 FIRE-Final Inspection11/13/200811/14/200811/14/2008 1:23:21 PMANR
Inspection for one portion of the remodel area work completed including the reception/waiting rooms, hall 118, cast rm., lymph. room, and some exam rooms. Need project related fire sprinkler work repairs, need to add an additional PFE for the east side as discussed, some missing door hardware.
FIR08-00544 INSP-Final Inspection11/13/200811/14/200811/14/2008 1:15:10 PMAFAIL
Noted obstructed pendent head at exam room 124, missing one head to be added per approved drawings at the hallway vestibule, see locations annotated on stamped plan set.