Inspections for the day of: Monday, November 14, 2011.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-02337 Final11/14/201111/14/201111/14/2011 3:02:42 PMPNH
thank you Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe called, locked up, will recall
ELE11-02516 Final11/14/201111/14/201111/14/2011 2:52:08 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Seth Stears called, told electrician to check derate, provide breaker closures for deadfront, label disconnects, drive in groubd rods, provide plastic ground abrasion protection, ground bushings for chase nipples
ELE11-02543 Rough-In Permanent Service11/14/201111/14/201111/14/2011 2:38:23 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Kathy Smith corrections made, ri ok, p/s u/g n ok
ELE11-02205 Final11/13/201111/14/201111/14/2011 1:44:24 PMAPASS
Phone #: ###-#### >> Inspection requested via web by Tracy Robertson ok final
ELE11-02554 Conference11/14/201111/14/201111/14/2011 12:37:27 PMPDONE
Please call 20min prior for access---Don Phone #: ###-#### talked about room addition wiring, when to call for ri, owner only doing wiring
ELE11-02004 Final11/10/201111/14/201111/14/2011 10:30:53 AMAPASS
Contact is Sean Sivesind ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Campbell ok final, no card to sign
ELE10-01493 Final11/10/201111/14/201111/14/2011 10:29:11 AMAPASS
van Phone #: ###-#### ok final
ELE08-00828 Final11/10/201111/14/201111/14/2011 9:43:57 AMAFAIL
Dave Phone #: ###-#### >> Inspection requested via web by Sean DeLacy called, left correction notice, NEC 110.26(F)(1) there shall be no foreign piping in dedicated space, 110.22 shall identify equipment, 358.30 shall secure emt within 3' of box, 408.4 shall provide panel schedules
ELE08-00318 Final11/10/201111/14/201111/14/2011 9:40:52 AMAFAIL
Dave Phone #: ###-#### >> Inspection requested via web by Sean DeLacy called, left correction notice, NEC 110.26(F)(1) there shall be no foreign piping in dedicated space, 110.22 shall identify equipment, 110.12(A) shall close unused openings, 258.30 shall secure emt within 3' of box, 408.4 shall provide panel schedules
ELE11-02485 Permanent Service11/10/201111/14/201111/14/2011 8:30:37 AMAPASS
bill Phone #: ###-#### p/s o/h rec ok
ELE11-02543 Rough-In Permanent Service11/11/201111/14/201111/14/2011 8:16:47 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Kathy Smith called, left correction notice, NEC 210.52(A)(1) no point along wall shall be over 6 ' from outlet (stairs), 334.30 nm cable shall be secured within 12" of panel, 314.17(c) 8" box in garage, 334.23 shall protect cable within 6' of attic access in garage