ELE11-02337
| Final | 11/14/2011 | 11/14/2011 | 11/14/2011 3:02:42 PM | P | NH |
|
|
thank you Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe called, locked up, will recall
|
ELE11-02516
| Final | 11/14/2011 | 11/14/2011 | 11/14/2011 2:52:08 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Seth Stears called, told electrician to check derate, provide breaker closures for deadfront, label disconnects, drive in groubd rods, provide plastic ground abrasion protection, ground bushings for chase nipples
|
ELE11-02543
| Rough-In Permanent Service | 11/14/2011 | 11/14/2011 | 11/14/2011 2:38:23 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Kathy Smith corrections made, ri ok, p/s u/g n ok
|
ELE11-02205
| Final | 11/13/2011 | 11/14/2011 | 11/14/2011 1:44:24 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Tracy Robertson ok final
|
ELE11-02554
| Conference | 11/14/2011 | 11/14/2011 | 11/14/2011 12:37:27 PM | P | DONE |
|
|
Please call 20min prior for access---Don Phone #: ###-#### talked about room addition wiring, when to call for ri, owner only doing wiring
|
ELE11-02004
| Final | 11/10/2011 | 11/14/2011 | 11/14/2011 10:30:53 AM | A | PASS |
|
|
Contact is Sean Sivesind ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Campbell ok final, no card to sign
|
ELE10-01493
| Final | 11/10/2011 | 11/14/2011 | 11/14/2011 10:29:11 AM | A | PASS |
|
|
van Phone #: ###-#### ok final
|
ELE08-00828
| Final | 11/10/2011 | 11/14/2011 | 11/14/2011 9:43:57 AM | A | FAIL |
|
|
Dave Phone #: ###-#### >> Inspection requested via web by Sean DeLacy called, left correction notice, NEC 110.26(F)(1) there shall be no foreign piping in dedicated space, 110.22 shall identify equipment, 358.30 shall secure emt within 3' of box, 408.4 shall provide panel schedules
|
ELE08-00318
| Final | 11/10/2011 | 11/14/2011 | 11/14/2011 9:40:52 AM | A | FAIL |
|
|
Dave Phone #: ###-#### >> Inspection requested via web by Sean DeLacy called, left correction notice, NEC 110.26(F)(1) there shall be no foreign piping in dedicated space, 110.22 shall identify equipment, 110.12(A) shall close unused openings, 258.30 shall secure emt within 3' of box, 408.4 shall provide panel schedules
|
ELE11-02485
| Permanent Service | 11/10/2011 | 11/14/2011 | 11/14/2011 8:30:37 AM | A | PASS |
|
|
bill Phone #: ###-#### p/s o/h rec ok
|
ELE11-02543
| Rough-In Permanent Service | 11/11/2011 | 11/14/2011 | 11/14/2011 8:16:47 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Kathy Smith called, left correction notice, NEC 210.52(A)(1) no point along wall shall be over 6 ' from outlet (stairs), 334.30 nm cable shall be secured within 12" of panel, 314.17(c) 8" box in garage, 334.23 shall protect cable within 6' of attic access in garage
|