ELE11-02564
| Rough-In Permanent Service | 11/14/2011 | 11/14/2011 | 11/14/2011 3:03:11 PM | P | PASS |
|
|
Rough in. Ryan is contact. Thank you Phone #: ###-#### >> Inspection requested via web by Chris Chesnut. P/S Connect ok. Ok to cover.
|
ELE11-02049
| Electrical Rough-In | 11/14/2011 | 11/14/2011 | 11/14/2011 2:43:19 PM | P | PASS |
|
|
Justin Phone #: ###-####
|
GCE11-00136
| GCE-Temporary Service | 11/10/2011 | 11/14/2011 | 11/14/2011 1:36:42 PM | A | PASS |
|
|
Matt @ ###-####. T/S Connect ok. Need to see after loads are hooked up.
|
GCE11-00133
| GCE-Rough-In | 11/10/2011 | 11/14/2011 | 11/14/2011 1:08:23 PM | A | PASS |
|
|
Heath @ ###-####
|
GCE11-00114
| GCE-Rough-In | 11/10/2011 | 11/14/2011 | 11/14/2011 12:37:09 PM | A | FAIL |
|
|
Steve @ ###-####. NEC 300.4 d Wire needs to be stapled in the middle of the stud. NEC 300.4 a1Nailplates. NEC 110.3b Listed and labelled. Light fixture above shower.
|