FIR12-00365
| INSP-Supply line flush | 11/14/2012 | 11/14/2012 | 11/14/2012 3:46:27 PM | P | PASS |
|
|
The underground supply line flush passed.
|
FIR12-00431
| INSP-Final Inspection | 11/13/2012 | 11/14/2012 | 11/14/2012 3:12:41 PM | P | PASS |
|
|
permit finaled
|
FIR12-00547
| INSP-Final Inspection | 11/14/2012 | 11/14/2012 | 11/14/2012 2:28:00 PM | P | PASS |
|
|
Permit finaled. The duct smoke detector power is now supplied from a separater 110 volt circuit and not from the fire alarm control panel.
|
FIR12-00231
| INSP-Final Inspection | 11/13/2012 | 11/14/2012 | 11/14/2012 2:24:11 PM | A | CANC |
|
|
Was at inspection at 7am but the manager was not available. To be rescheduled for friday afternoon per alex Phone #: ###-####
|
FIR12-00365
| INSP-Sprinkler Rough-in | 11/13/2012 | 11/14/2012 | 11/14/2012 2:10:16 PM | A | PASS |
|
|
The entry lobby sprinkler piping is ok to re-cover. Tim Frost approved as-builts have been marked up by me for location and have been left on the job site with the sprinkler fitter.
|
FIR12-00494
| INSP-Final Inspection | 11/13/2012 | 11/14/2012 | 11/14/2012 11:58:17 AM | A | FAIL |
|
|
Prior to a final for this permit the ceiling and related pendant sprinkler protection needs to be installed in the two electrical rooms.
|
BLD12-01915
| FIRE-Final Inspection | 11/13/2012 | 11/14/2012 | 11/14/2012 11:25:50 AM | A | FAIL |
|
|
The project related fire alarm permit needs finaled. It appears sprinkler protection is needed under the new overhead door at the Smoker. All of the exit signs are non functional. One exit sign needs to be added at the main exit/arch and another at the exit door at the Bar. Repair the non-functional emergency lights. Raise the K class extinguisher in the kitchen to be off the floor. Remove the manaual dead bolt at the freezer door. Provide corrected occupant load sign and contrasting colors for the address numbers.
|
BLD12-02684
| FIRE-Final Inspection | 11/13/2012 | 11/14/2012 | 11/14/2012 11:18:08 AM | A | PASS |
|
|
Life safety passed
|
FIR12-00630
| INSP-Final Inspection | 11/13/2012 | 11/14/2012 | 11/14/2012 10:17:33 AM | A | PASS |
|
|
Permit finaled. Hood suppression system functioned correctly
|
FIR12-00629
| INSP-Final Inspection | 11/13/2012 | 11/14/2012 | 11/14/2012 10:17:07 AM | A | PASS |
|
|
Permit finaled. Hood suppression system functioned correctly
|
BLD12-02852
| FIRE-Final Inspection | 11/13/2012 | 11/14/2012 | 11/14/2012 9:48:45 AM | A | PASS |
|
|
life safety passed
|