Inspections for the day of: Thursday, November 14, 2013.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-03179 Permanent Service11/13/201311/14/201311/14/2013 2:37:55 PMPPASS
We are going to be on site with Idaho Power to refeed service to trailer house. We are meeting at 10:30 to start the work and would like to have someone available for an on call status to keep this elderly couple from being without power for as little as necessary. Hoping by 12:30 or close. Please call and confirm. Thank you! Phone #: ###-#### >> Inspection requested via web by Clay Jackson p/s u/g rec ok
ELE13-03188 Final11/14/201311/14/201311/14/2013 1:36:38 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Brad Baker NEC 210.8(B)(2) KItchens All 15 and 20 ampere 120 volt receptacles require GFCI protection
ELE13-03180 Electrical Rough-In11/14/201311/14/201311/14/2013 1:05:12 PMPNR
underground Phone #: ###-#### >> Inspection requested via web by Louis Keller Contractor will reschedule for PM11/15/13
ELE13-02447 Final11/14/201311/14/201311/14/2013 12:52:58 PMPPASS
Key for entry in front outlet Phone #: ###-#### >> Inspection requested via web by TOM BICANDI correction done Thank you! final ok
ELE13-03189 Final11/14/201311/14/201311/14/2013 12:35:14 PMPFAIL
devices were cut into the existing wall no need for rough in inspection final is ready Phone #: ###-#### >> Inspection requested via web by Brad Baker Kitchens NEC 210.8(B)(2) All 15 and 20 ampere 120 volt receptacles require GFCI protection.
GCE13-00194 GCE-Rough-In11/13/201311/14/201311/14/2013 12:11:43 PMPNR
Jim ###-#### not ready
ELE13-03162 Temporary Service11/13/201311/14/201311/14/2013 11:50:00 AMPPASS
Vince Phone #: ###-#### t/s o/h n ok
ELE12-00151 ELE-Aging Inspection11/14/201311/14/201311/14/2013 11:15:08 AM DONE
see final
ELE12-00151 Final11/14/201311/14/201311/14/2013 11:14:40 AMPPASS
ok final
ELE13-02715 Final11/13/201311/14/201311/14/2013 10:46:34 AMAPASS
call me before you head there so I can make sure the owner will be there Phone #: ###-#### >> Inspection requested via web by Neal Rumsey final ok
ELE13-03183 Final11/13/201311/14/201311/14/2013 10:45:35 AMAPASS
wired ac Phone #: ###-#### >> Inspection requested via web by PAT MILLER final ok
ELE13-03183 Electrical Rough-In11/13/201311/14/201311/14/2013 10:43:22 AMAPASS
wired ac Phone #: ###-#### >> Inspection requested via web by PAT MILLER rough-in out standing ok
ELE13-03150 Temporary Service11/13/201311/14/201311/14/2013 9:46:45 AMAPASS
Temp pole Phone #: ###-#### >> Inspection requested via web by TOM BICANDI t/s o/h n ok
GCE13-00193 GCE-Rough-In11/13/201311/14/201311/14/2013 9:28:45 AMAFAIL
Jim ###-#### NEC 334.30 NM cable requires securing within 8 in. of receptacle box and 12 in. of service panel. secure SER cable. NEC 110.9 Available Fault current from tranformer
GCE13-00190 GCE-Permanent Service11/12/201311/14/201311/14/2013 8:52:19 AMAPASS
Brent ###-#### p/s o/h rec ok
ELE13-02447 Final11/13/201311/14/201311/14/2013 8:24:44 AMAFAIL
Key in front outlet box for access Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Energy code requires at least 50% compac florscent luminaires