ELE16-02986
| Final | 11/10/2016 | 11/14/2016 | 11/14/2016 3:02:08 PM | P | PASS |
|
|
Call if necessary. Phone #: ###-#### Inspection requested via web by Samatha Solberg Final ok
|
ELE16-02180
| Final | 11/11/2016 | 11/14/2016 | 11/14/2016 2:16:05 PM | P | PASS |
|
|
Call Mitch 30 minutes prior. Phone #: ###-#### Inspection requested via web by Mitch Whited Final ok
|
ELE16-02247
| Electrical Rough-In | 11/11/2016 | 11/14/2016 | 11/14/2016 1:07:41 PM | A | PASS |
|
|
Patio cover. Walk around east side to back yard. Phone #: ###-#### Inspection requested via web by mike brown Back patio rough in ok cover
|
ELE16-03673
| Rough-In Permanent Service | 11/14/2016 | 11/14/2016 | 11/14/2016 12:40:57 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey 110.3- Service feeders not installed. 210.52(A)- Receptacle outlet shall be installed for 6' wall space to right of fireplace. 210.52(B)- Pantry counter top shall have receptacle outlet layout same as kitchen. 210.52(D)- Master bath vanity receptacle is placed behind wall and will ot be in place to serve basin. 250.110- Equipment ground shall be connected in temp connection of furnaces and abrasion protection shall be present as per 300.4. IBC- Boxes for soffit cans shall be down to soffit material for air seal. 590.6- 50 amp GFCI receptacle in temp pole will not trip.
|
ELE16-03673
| Final | 11/10/2016 | 11/14/2016 | 11/14/2016 12:34:49 PM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey Needed rough in and permanant service.
|
ELE16-03665
| Electrical Rough-In | 11/10/2016 | 11/14/2016 | 11/14/2016 11:27:19 AM | A | PASS |
|
|
Drive by to verify dry sheeting on roof complete for wiring installed front and rear patios. Contact Bob ###-#### Job dry sheeting complete. Soffits ok
|
ELE16-03547
| Rough-In Permanent Service | 11/10/2016 | 11/14/2016 | 11/14/2016 9:31:52 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|
ELE15-02641
| Final | 11/10/2016 | 11/14/2016 | 11/14/2016 8:44:58 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton No card posted. Final ok
|
ELE16-03489
| Final | 11/12/2016 | 11/14/2016 | 11/14/2016 8:44:19 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Final ok
|
ELE16-03489
| Electrical Rough-In | 11/12/2016 | 11/14/2016 | 11/14/2016 8:43:52 AM | A | PASS |
|
|
ceiling grid Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Grid rough in ok cover
|