PLM16-04127
| Water Heater Final | 11/14/2016 | 11/14/2016 | 11/14/2016 3:03:45 PM | P | PASS |
|
|
Would like Mid PM and Call when on way. Thank you Phone #: ###-#### Inspection requested via web by Xanti Berria
|
MEC16-05043
| Final | 11/14/2016 | 11/14/2016 | 11/14/2016 3:03:28 PM | P | PASS |
|
|
Would like Mid PM and a call when on way. Thank you! Phone #: ###-#### Inspection requested via web by Xanti Berria
|
PLM16-03983
| Final | 11/11/2016 | 11/14/2016 | 11/14/2016 2:43:40 PM | P | PART |
|
|
Please call Derek 45 mins prior to arrival Phone #: ###-#### Inspection requested via web by Kassy Goodwin-OK to cover, dbca needs tested.
|
PLM16-04145
| Water and/or Sewer | 11/14/2016 | 11/14/2016 | 11/14/2016 2:25:06 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Chad Cannon
|
PLM16-04145
| DOC - Permit Finaled | 11/14/2016 | 11/14/2016 | 11/14/2016 2:24:56 PM | P | PASS |
|
|
|
PLM16-04141
| Plumbing Rough-in | 11/13/2016 | 11/14/2016 | 11/14/2016 2:14:11 PM | P | PASS |
|
|
We just changed copper water lines out in the walls 2Pac install a waste and overflow on a new tub the customer provided installed the customer shower valve that they provided and changed out the toilet flange upgraded the lab drain from inch and a quarter to inch and a half working pressure on water lines and drain test on bathroom tub YouTube Just replacing a few sections of pipe and the toilet is already hooked up and working Phone #: ###-#### Inspection requested via web by Mark Kelso
|
PLM16-04035
| Plumbing Rough-in | 11/9/2016 | 11/14/2016 | 11/14/2016 2:00:50 PM | P | PART |
|
|
please call Jeremy prior to arriving Phone #: ###-#### Inspection requested via web by Nicholas Paige-Phase 1 inwall DWV and water and overhead venting and water except water tie-in pass. No under flr piping yet.
|
PLM16-04109
| Groundwork | 11/14/2016 | 11/14/2016 | 11/14/2016 1:22:36 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by casey lattimer
|
PLM16-04108
| Groundwork | 11/14/2016 | 11/14/2016 | 11/14/2016 1:22:17 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by casey lattimer
|
PLM16-04107
| Groundwork | 11/14/2016 | 11/14/2016 | 11/14/2016 1:22:03 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by casey lattimer
|
PLM16-04106
| Groundwork | 11/14/2016 | 11/14/2016 | 11/14/2016 1:21:41 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by casey lattimer
|
PLM16-04142
| Water and/or Sewer | 11/14/2016 | 11/14/2016 | 11/14/2016 1:06:40 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by matt ford
|
PLM16-04142
| DOC - Permit Finaled | 11/14/2016 | 11/14/2016 | 11/14/2016 1:06:26 PM | P | PASS |
|
|
|
PLM16-04127
| Water and/or Sewer | 11/14/2016 | 11/14/2016 | 11/14/2016 12:41:14 PM | P | CANC |
|
|
Would like Mid PM and Call when on way. Thank you Phone #: ###-#### Inspection requested via web by Xanti Berria
|
PLM16-03372
| Final | 11/14/2016 | 11/14/2016 | 11/14/2016 12:40:10 PM | A | FAIL |
|
|
Inspection requested via web by Brian Johansen-Water heater needs to meet a 67 first hr reovery rate. Water heater installed only has a 54.
|
PLM16-03628
| Plumbing Rough-in | 11/11/2016 | 11/14/2016 | 11/14/2016 12:11:20 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Nels Moore
|
PLM16-04104
| Plumbing Rough-in | 11/10/2016 | 11/14/2016 | 11/14/2016 11:21:32 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Semsudin Konjuhovac
|
PLM16-03490
| Final | 11/10/2016 | 11/14/2016 | 11/14/2016 11:09:01 AM | A | PASS |
|
|
Homeowner or other contractors should be there. If not please give me a call. ###-####. Thanks. Phone #: ###-#### Inspection requested via web by Josh Johnson
|
PLM16-03422
| Final | 11/11/2016 | 11/14/2016 | 11/14/2016 10:56:51 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dennis Seward
|
PLM16-03849
| Final | 11/14/2016 | 11/14/2016 | 11/14/2016 10:56:33 AM | P | PASS |
|
|
|
PLM16-03628
| Roof Drains | 11/11/2016 | 11/14/2016 | 11/14/2016 10:35:30 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Nels Moore
|
PLM16-03628
| Other | 11/11/2016 | 11/14/2016 | 11/14/2016 10:35:02 AM | A | PASS |
|
|
gas line pressure test Phone #: ###-#### Inspection requested via web by Nels Moore-60 lb gas test pass
|
MEC16-03699
| Final | 11/11/2016 | 11/14/2016 | 11/14/2016 9:47:32 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino
|
MEC16-04884
| Pressure Test | 11/10/2016 | 11/14/2016 | 11/14/2016 9:46:19 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Matthew Grant-Gas gauge will not zero out. Test on flue fail.
|
MEC16-04884
| Rough-in | 11/10/2016 | 11/14/2016 | 11/14/2016 9:45:21 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Matthew Grant-Insulation sheild requires a 1" clearance around B-vent. 8" fresh air needs to come off the return air plenum.
|
MEC16-05027
| Rough-in | 11/11/2016 | 11/14/2016 | 11/14/2016 9:43:09 AM | A | PASS |
|
|
LARRY ###-#### Phone #: ###-#### Inspection requested via web by Jason Robinson
|
MEC16-03900
| Final | 11/10/2016 | 11/14/2016 | 11/14/2016 9:08:02 AM | A | PASS |
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek
|
PLM16-03318
| Final | 11/11/2016 | 11/14/2016 | 11/14/2016 9:07:48 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rob Bristol
|
MEC16-04074
| Final | 11/10/2016 | 11/14/2016 | 11/14/2016 9:07:26 AM | A | PASS |
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek
|
PLM16-03171
| Final | 11/11/2016 | 11/14/2016 | 11/14/2016 9:07:07 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rob Bristol
|
PLM16-03133
| Final | 11/10/2016 | 11/14/2016 | 11/14/2016 8:47:59 AM | A | CANC |
|
|
Call for access // Jacob Phone #: ###-####
|
MEC16-05046
| Pressure Test | 11/11/2016 | 11/14/2016 | 11/14/2016 8:47:47 AM | A | NR |
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek-No gas piping installed yet.
|
MEC16-05046
| Rough-in | 11/11/2016 | 11/14/2016 | 11/14/2016 8:47:12 AM | A | FAIL |
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek-Insulation sheild needs to have a 1" clearance around b-vent.
|
MEC16-05033
| Rough-in | 11/10/2016 | 11/14/2016 | 11/14/2016 8:43:35 AM | P | CANC |
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### >> Inspection requested via web by Dawn Kalsbeek Inspection cancelled from web by: Dawn Kalsbeek
|
MEC16-05051
| Rough-in | 11/11/2016 | 11/14/2016 | 11/14/2016 8:28:07 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dan Otero
|
MEC16-04888
| Pressure Test | 11/10/2016 | 11/14/2016 | 11/14/2016 8:27:53 AM | A | PASS |
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek-20 lb gas test pass
|
MEC16-04888
| Rough-in | 11/10/2016 | 11/14/2016 | 11/14/2016 8:27:21 AM | A | PASS |
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek
|
MEC16-05033
| Rough-in | 11/14/2016 | 11/14/2016 | 11/14/2016 8:27:02 AM | A | FAIL |
|
|
Need access to furnace in attic and missing nailplates on condensate.
|
MEC16-05033
| Pressure Test | 11/10/2016 | 11/14/2016 | 11/14/2016 8:26:06 AM | A | PASS |
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek-20 lb gas test pass
|
MEC16-05049
| Rough-in | 11/11/2016 | 11/14/2016 | 11/14/2016 8:20:36 AM | A | PASS |
|
|
Inspection requested via web by Dan Otero
|
PLM15-01014
| PLM-Aging Inspection | 11/14/2016 | 11/14/2016 | 11/14/2016 6:20:59 AM | | PART |
|
|
No calls
|
PLM15-03955
| PLM-Aging Inspection | 11/14/2016 | 11/14/2016 | 11/14/2016 6:20:19 AM | | PART |
|
|
WIP
|
PLM16-01664
| PLM-Aging Inspection | 11/14/2016 | 11/14/2016 | 11/14/2016 6:19:34 AM | | PART |
|
|
No calls
|