FIR17-00716
| INSP-Alarm Testing | 11/14/2018 | 11/14/2018 | 11/14/2018 12:00:00 AM | A | FAIL |
|
|
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
On site 9:30 am with Nathan. Tested unit detectors and sounder for floors 2 - 5. Rooms requiring retest include 207,8,9,16, 315, 408, 503 and 506. Still to test is general alarm notification, corridor detection, manual alarm, all devices on 1st floor and garage, elevator recall and shunt, central station monitoring and batteries. Room on 1st floor is missing a pull box cover. Waterflow devices are missing covers.
On site 4:30 - 7:00 pm with Nathan and Adam Bayne. All remaining items tested and functioned. During general alarm, dwelling unit audible notificaiton did not sync with common area audible notificaiton. 11-15-18 discussed this issue with Ron Johnson.
|
FIR18-00462
| INSP-Final Inspection | 11/12/2018 | 11/14/2018 | 11/14/2018 12:00:00 AM | P | PASS |
|
|
John Howard - Techinican Phone #: ###-#### >> Inspection requested via web by John Siewert
All notification, 2 waterflows and 2 tampers, 1 manual alarm, 1 smoke and central station monitoring tested. All functioned properly. Record of completion and as built drawings required.
|