Inspections for the day of: Wednesday, November 14, 2018.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorLee G Meredith
TitleFIRE ALARM REVIEWER
Phone #208-608-7112
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00716 INSP-Alarm Testing11/14/201811/14/201811/14/2018 12:00:00 AMAFAIL
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
On site 9:30 am with Nathan. Tested unit detectors and sounder for floors 2 - 5. Rooms requiring retest include 207,8,9,16, 315, 408, 503 and 506. Still to test is general alarm notification, corridor detection, manual alarm, all devices on 1st floor and garage, elevator recall and shunt, central station monitoring and batteries. Room on 1st floor is missing a pull box cover. Waterflow devices are missing covers.

On site 4:30 - 7:00 pm with Nathan and Adam Bayne. All remaining items tested and functioned. During general alarm, dwelling unit audible notificaiton did not sync with common area audible notificaiton. 11-15-18 discussed this issue with Ron Johnson.
FIR18-00462 INSP-Final Inspection11/12/201811/14/201811/14/2018 12:00:00 AMPPASS
John Howard - Techinican Phone #: ###-#### >> Inspection requested via web by John Siewert

All notification, 2 waterflows and 2 tampers, 1 manual alarm, 1 smoke and central station monitoring tested. All functioned properly. Record of completion and as built drawings required.