ELE00-01560
| Electrical Rough-In | 11/13/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 11/13/2000 at 11:48:06. Contact: ###-####. areas 1 & 2, first floor ele r/i. 11/15/2000 9:29:38 PM
|
ELE00-04391
| Permanent Service | 11/13/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | A | PASS |
|
|
PER SER BILL-- ###-####. meter/main service panel. 11/15/2000 9:39:58 PM
|
ELE00-04316
| Electrical Rough-In | 11/14/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | A | PART |
|
|
pager ###-####. ele r/i; perm serv. not ready. 11/15/2000 9:36:59 PM
|
ELE00-04397
| Temporary Service | 11/14/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | A | PASS |
|
|
chris ###-####. temporary service pole. 11/15/2000 9:35:30 PM
|
ELE00-04398
| Temporary Service | 11/14/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | A | PASS |
|
|
chris ###-####. temporary service pole. 11/15/2000 9:36:06 PM
|
ELE00-04175
| Final | 11/14/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | A | PASS |
|
|
###-####. completed. 11/15/2000 9:30:12 PM
|
ELE00-04394
| Electrical Rough-In | 11/14/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | A | PASS |
|
|
Dave ###-####. p.v.c. conduit underslab. ok 11/15/2000 9:34:48 PM
|
ELE00-03783
| Electrical Rough-In | 11/14/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | A | PART |
|
|
conference and rough in Becky ###-####. shell and core; bathroom & corridor ele r/i. 11/15/2000 9:32:24 PM
|
ELE00-03786
| Electrical Rough-In | 11/14/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | A | PART |
|
|
Becky ###-####. tenant improvement; ele r/i. 11/15/2000 9:33:33 PM
|
ELE00-00869
| Final | 11/14/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/14/2000 at 18:05:45. Contact: ###-####. occupied by tenant; unable to inspect some areas: Furniture, desks, etc. 11/15/2000 9:39:02 PM
|
ELE00-04422
| Permanent Service | 11/15/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | A | FAIL |
|
|
###-#### bob final 11/15/2000 9:53:46 PM. 230-24 exception #2: service entrance conductors shall clear roof at least 3ft.. 110-26. service equiptment shall be clear from grade to 6ft above top of equiptment. posted, called contractor. 11/17/2000 12:30:35 PM
|
ELE00-03907
| Final | 11/15/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 403 On 11/15/2000 9:51:58 PM completed.
|
ELE00-00033
| Final | 11/15/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/15/2000 at 07:55:10. Contact: ###-####. completed. 11/15/2000 9:56:49 PM
|
ELE00-04003
| Electrical Rough-In | 11/15/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | P | PASS |
|
|
re-insp r/i -- ###-#### daniel. main service panel; ufer grounding conductor ok. 11/15/2000 9:58:58 PM
|
ELE00-04004
| Electrical Rough-In | 11/15/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | P | PASS |
|
|
daniel---###-#### r/i . main service; ufer grounding conductor ok. 11/15/2000 9:58:07 PM
|
ELE00-04382
| Electrical Rough-In | 11/15/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/15/2000 at 10:42:58. Contact: ###-####. 4th floors; walls ele r/i. 11/16/2000 5:07:08 PM
|
ELE00-04340
| Electrical Rough-In | 11/14/2000 | 11/15/2000 | 11/15/2000 12:00:00 AM | P | CANC |
|
|
r/i ###-####. not ready, will reschedule. 11/15/2000 9:41:08 PM
|