Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE00-04399 Rough-In Permanent Service11/14/200011/15/200011/15/2000 12:00:00 AMAPASS
BRANDON ###-#### R/I & SER p/s u/g n ok - ok cover ri 11/15/2000 4:50:22 PM
ELE00-04401 Rough-In Permanent Service11/14/200011/15/200011/15/2000 12:00:00 AMAPASS
###-#### p/s u/g n ok - ok cover ri 11/15/2000 4:43:05 PM
ELE00-04404 Temporary Service11/14/200011/15/200011/15/2000 12:00:00 AMAPASS
Terry ###-#### t/s u/g n ok 11/15/2000 4:49:28 PM
ELE00-01759 Final11/14/200011/15/200011/15/2000 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 11/14/2000 at 14:16:01. Contact: ###-####. no access 11/15/2000 12:00:00 PM
ELE00-04091 Final11/14/200011/15/200011/15/2000 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 11/14/2000 at 14:17:02. Contact: ###-####. no access 11/15/2000 11:59:06 AM
ELE00-03539 Final11/14/200011/15/200011/15/2000 12:00:00 AMAFAIL
fn --a j ###-#### corr. nec 210-52(a)(1)-210-52(c)(1)-210-8(a)(1)-110-3(b) shall have sgl pole brks on single curcuits bbc timer on all house fan 11/15/2000 4:48:00 PM
ELE00-04250 Electrical Rough-In11/14/200011/15/200011/15/2000 12:00:00 AMAPASS
of the spring pool look at the bonding Brenda ###-#### ok pool bonding 11/15/2000 4:48:43 PM
ELE00-02341 Final11/15/200011/15/200011/15/2000 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 11/15/2000 at 07:43:00. Contact: ###-####. corr. nec210-52(a)(1) outlets missing in master bedrm,kitchen wall,dinning rm.,family & 430-102(b) dishwasher 11/15/2000 4:57:44 PM
ELE00-03992 Temporary Service11/15/200011/15/200011/15/2000 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 11/15/2000 at 07:50:31. Contact: . wrong permit 11/15/2000 12:19:28 PM
ELE00-03776 Final11/15/200011/15/200011/15/2000 12:00:00 AMPPASS
fn pat ###-#### --call 1st before insp ok final 11/16/2000 4:34:13 PM
ELE00-03076 Final11/15/200011/15/200011/15/2000 12:00:00 AMPNR
for homeowner craig-- ###-#### cell-- fn call 1st before insp nr needs proper lgt in closet needs gfci in kitchen 11/15/2000 4:51:28 PM
ELE00-04366 Rough-In Permanent Service11/15/200011/15/200011/15/2000 12:00:00 AMPCANC
###-#### CHRIS R/I & SER completed 11/13/00 11/15/2000 12:03:22 PM
ELE00-01759 Final11/15/200011/15/200011/15/2000 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 11/15/2000 at 09:52:21. Contact: ###-####. ok final 11/15/2000 4:53:48 PM
ELE00-04091 Final11/15/200011/15/200011/15/2000 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 11/15/2000 at 09:53:24. Contact: ###-####. ok final 11/15/2000 4:54:17 PM
ELE00-04427 Rough-In Permanent Service11/15/200011/15/200011/15/2000 12:00:00 AMPPART
brandon ###-#### ok cover ri - service fail no u-fer ground 11/15/2000 4:53:24 PM
ELE00-03546 Final11/15/200011/15/200011/15/2000 12:00:00 AMPPASS
###-#### left survey 11/16/2000 4:35:01 PM