Inspections for the day of: Friday, November 15, 2002.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-02528 Final11/14/200211/15/200211/15/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 11/14/2002 at 10:43:10. Contact: ###-####. ok 11/15/2002 10:36:15 AM
ELE02-02641 Final11/14/200211/15/200211/15/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 11/14/2002 at 12:03:52. Contact: .
no final till homeowner secures electrical permit for work on garage PM#bld02-01813 per note on structrual permit 11/15/2002 1:51:26 PM
ELE02-03472 Final11/14/200211/15/200211/15/2002 12:00:00 AMACANC
###-#### GARY called could not hear message called orther number no contact, cor posted 250.53 (B) grd rod not 6ft apart,250.92 (A)(3) bond both ends of nipple between meter and p/s when GEC passes through it. 312.3 service panel shall be flush with finish surface and cover fit tight to panel,250.52 or 104 grd within 5 ft or bond 11/15/2002 2:26:30 PM
ELE02-03322 Final11/14/200211/15/200211/15/2002 12:00:00 AMACANC
dawn; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie see added r/i 11/15/2002 12:39:10 PM
ELE02-03176 Final11/15/200211/15/200211/15/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 11/15/2002 at 07:27:46. Contact: ###-####. cor. posted met with contractor 314.20 250.146(A) boxes with raised covers, 300.11 use own support wires too support raceways in grid ceiling, 300.7 seal conduits entering cooler,, 250.6 arrange wires in conduits to contacter to prevent objectionable currents, 110.12(A) seal unused KOs cor. posted to BLD02-02261 support low voltage cables laying on grid ceiling $42.00 reinspection fee due 11/15/2002 11:42:55 AM
ELE02-03322 Electrical Rough-In11/15/200211/15/200211/15/2002 12:00:00 AMAPASS
r/i for garage ok
ELE02-03472 Permanent Service11/15/200211/15/200211/15/2002 12:00:00 AMAFAIL
see final inspection request for correction info
ELE02-01024 Final11/12/200211/15/200211/15/2002 12:00:00 AMPCANC
###-#### CHRISTI called no access person at house did not have key,, they will call for reinspection at a later date 11/15/2002 4:49:45 PM
ELE02-03536 Electrical Rough-In11/13/200211/15/200211/15/2002 12:00:00 AMPPART
STEVE ###-#### OR CELL # ###-#### CONF ONLY ok 11/15/2002 3:36:53 PM
ELE02-03522 Electrical Rough-In11/15/200211/15/200211/15/2002 12:00:00 AMPPASS
###-#### ok still needs outlet too serve din. rm wall for proper spacing , will install at time of trim out 11/15/2002 2:50:35 PM
ELE02-01274 Electrical Rough-In11/15/200211/15/200211/15/2002 12:00:00 AMPPART
CONFERENCE FOR EXTENSION ONLY PLEASE CALL ###-#### ALLISON ok 11/15/2002 5:25:55 PM
ELE02-03558 Permanent Service11/15/200211/15/200211/15/2002 12:00:00 AMPPASS
dawn ###-#### p/s u/g rec. for meter ok 11/15/2002 4:11:53 PM