ELE04-03554
| Electrical Rough-In | 11/12/2004 | 11/15/2004 | 11/15/2004 12:00:00 AM | A | PASS |
|
|
Internet Inspection Request from: Jan Rice mike ###-#### 2 walls 2nd floor ok 11/15/2004 9:34:19 AM
|
ELE04-02811
| Final | 11/12/2004 | 11/15/2004 | 11/15/2004 12:00:00 AM | A | NH |
|
|
sunshine elect ###-#### notice posted called 11/15/2004 8:39:20 AM
|
ELE04-00459
| Rough-In Permanent Service | 11/12/2004 | 11/15/2004 | 11/15/2004 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Linda Hartwell 250.122 needs #10 grd for #10 wire, bond sprinkler system r/i ok p/s u/g new ok 11/15/2004 9:07:37 AM
|
ELE04-03563
| Electrical Rough-In | 11/12/2004 | 11/15/2004 | 11/15/2004 12:00:00 AM | A | PART |
|
|
Rich-Partial rough-in-in the floor, pvc conduit ; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner u/g for cash wrap 11/15/2004 10:26:08 AM
|
ELE04-03453
| Rough-In Permanent Service | 11/12/2004 | 11/15/2004 | 11/15/2004 12:00:00 AM | A | FAIL |
|
|
We ran a new 20 amp 240 volt 3 phase ckt.(Panel L3, ckt:18-20-22)to a receptacle for a table saw.This work is in the north-west building.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell called over 360 degrees of bends in 1/2 emt to table saw 11/15/2004 11:00:26 AM
|
ELE04-03543
| Electrical Rough-In | 11/13/2004 | 11/15/2004 | 11/15/2004 12:00:00 AM | A | NH |
|
|
Re-inspection. Corrections made.; Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA called left message 11/15/2004 8:11:00 AM
|
ELE04-00825
| Electrical Rough-In | 11/15/2004 | 11/15/2004 | 11/15/2004 12:00:00 AM | P | FAIL |
|
|
We'll be ready mid morning if you like to stop around 11:00 am. Otherwise the building will be open; Phone #: ###-#### Internet Inspection Request from: Monty Adkinson cor. posted called 300.4(A)(1)&(D), 314.3&110.3(B) 314.20, 314.16, 300.10, and 300.4(A)(1)&(D) for low voltage see cor. posted 11/15/2004 2:25:28 PM
|
ELE04-03188
| Final | 11/15/2004 | 11/15/2004 | 11/15/2004 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 11/15/2004 at 7:39:40 AM. Contact: ###-####. cor. posted called needs back feed clip breaker in shop, needs romex connector at fixtures if no box, or access hole in fixture to access box410.14(B) 11/15/2004 1:31:20 PM
|
ELE04-03576
| Final | 11/15/2004 | 11/15/2004 | 11/15/2004 12:00:00 AM | P | CANC |
|
|
Eric; Phone #: ###-#### Internet Inspection Request from: Jan Rice called wrong address, should be 11478 w franklin rd
11/15/2004 2:39:09 PM
|
ELE04-02930
| Final | 11/15/2004 | 11/15/2004 | 11/15/2004 12:00:00 AM | P | PASS |
|
|
Pat-Call 1/2 hr prior for access; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner ok card signed 11/15/2004 12:11:18 PM
|
ELE04-02934
| Final | 11/15/2004 | 11/15/2004 | 11/15/2004 12:00:00 AM | P | PASS |
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok card signed 11/15/2004 12:57:21 PM
|
ELE04-03517
| Temporary Service | 11/9/2004 | 11/15/2004 | 11/15/2004 12:00:00 AM | P | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Jeff Radford t/s for crane 11/15/2004 3:29:38 PM
|